Continued, Battery maintenance guidelines – Alpha Technologies BSM-3 Battery Side Module Enclosure User Manual
Page 8

Preface
8
033-082-C0-002 Rev. B
The battery maintenance instructions listed below are for reference only. Battery manufacturer’s
instructions for transportation, installation, storage or maintenance take precedence over these
instructions.
•
To prevent damage, inspect batteries every 3 months for:
Signs of battery cracking, leaking or swelling. The battery should be replaced immediately by
authorized personnel using a battery of the identical type and rating.
Signs of battery cable damage. Battery cable should be replaced immediately by Authorized
Personnel using replacement parts specified by vendor.
Loose battery connection hardware. Refer to battery manufacturer’s documentation for the
correct torque and connection hardware for the application.
•
Apply battery manufacturer’s specified antioxidant compound on all exposed connections.
•
Verify battery terminals and/or exposed connection hardware is not within 2 inches of a
conductive surface. Reposition batteries as necessary to maintain adequate clearance.
•
Clean up any electrolyte (battery emission) in accordance with all federal, state, and local
regulations or codes.
•
Proper venting of the enclosure is recommended. Follow the Battery Manufacturer’s approved
transportation and storage instructions.
•
Always replace batteries with those of an identical type and rating. Never install old or
untested batteries.
Battery Maintenance Guidelines
•
Prior to handling the batteries, touch a grounded metal object to dissipate any static charge that
may have developed on your body.
•
Never use uninsulated tools or other conductive materials when installing, maintaining, servicing
or replacing batteries.
•
Use special caution when connecting or adjusting battery cabling. An improperly connected
battery cable or an unconnected battery cable can make contact with an unintended surface that
can result in arcing, fire, or possible explosion.
•
A battery showing signs of cracking, leaking, or swelling should be replaced immediately by
Authorized Personnel using a battery of identical type and rating.
•
Under extreme overcharging conditions, Lead-acid batteries can vent a mixture of Hydrogen gas
which is explosive.
Battery Safety Notes,