2.0 Site Preparation

2.1 Site Considerations

• Where possible, select a site away from houses, and above the 100-year flood plain.
• Place in a shaded location to minimize the effects of solar loading.
• Avoid locating the enclosure where it obstructs or inhibits visibility.
• Locate the enclosure away from sprinkler systems, or other sources of forced water.
• Locate the enclosure out of the prevailing wind to minimize the buildup of snow or wind-

borne dust.

• Determine if soil conditions are suitable for the appropriate grounding system.
• Verify utility power cabling is terminated at the site.
• Ensure maintenance access and exhaust clearance.

• Locate the enclosure to allow for 36" of clearance around all enclosure door and exhaust

openings.

2.2 Acoustics

Nuisance noise is of concern to nearby residents. Nuisance noise is a directional noise

which can cause discomfort during engine-generator operation to nearby residential

occupants (audible levels may vary due to absorption and reflection caused by the immediate

surroundings).
Audible impact on neighborhoods is mitigated by recent advances in mufflers, flame resistant

sound materials, intake air sound attenuators, along with improved cabinet airflow dynamics.

The figures below show the measured audible levels from CE-3x2 5KW and PN-6x-T 7.5kW

generators at full load. Note the symmetry of these emissions. Deployment decisions must

include noise consideration to minimize nuisance noise.

Fig. 2-1, Generator Sound Levels at 100% Load

10'

20'

50'

70. 3

64. 3

56. 3

dB a

Feet

5'

10'

North East

71.4dBA

East

70.0dBA

North

73.0dBA

South East

70.5dBA

South

72.4dBA

South West

70.1BA

West

71.9dBA

North West

72.8dBA

Intake

Exhaust

CE-3x2

PN-6x-T