Table 7-7, heater mat oids and functionality, Table 7-8, heater mat mib reports, 12 configuring the battery heater mat controller – Alpha Technologies DSM3 for XM2 - Technical Manual User Manual
Page 70: 0 installation

70
745-814-B8-001, Rev. C (03/2014)
7.0 Installation
Once the connection has been made, Environmental Control Management can be configured
using an SNMP MIB browser as indicated in the following tables. The Environmental Control MIB
section begins at atiMgmtSysTempMgr (1.3.6.1.4.1.926.1.3.2.4). Status of the Environmental
Control is also available via the Communications Module’s Web page by navigating to ‘Advanced
Configuration’, ‘I/O – Environment’. Ensure the ‘Heater/Cooler Only’ is selected from the drop-
down list.
Set these OIDs to the specified value
Functionality
atiMgmtSysTempTemperature (1.3.6.1.4.1.926.1.3.2.4.5) to 5
Heater turns on at 5°C
atiMgmtSysTempHysteresis (1.3.6.1.4.1.926.1.3.2.4.6) to 3
3°C of permitted controller overshoot (in this case, would turn off at 8°C)
atiMgmtSysTempCtrl (1.3.6.1.4.1.926.1.3.2.4.1) to 3
Battery temperature sensor used to control heater setpoint
atiMgmtSysTempMode (1.3.6.1.4.1.926.1.3.2.4.3) to 1
Places controller in heater mode
atiMgmtSysTempActiveState (1.3.6.1.4.1.926.1.3.2.4.4) to 1
Drive pin to the temperature device will go low when heater is on
atiMgmtSysTempStatusInvert (1.3.6.1.4.1.926.1.3.2.4.9) to 1
Sets the polarity of the feedback signal from the temperature device
During operation, the following MIB points will report the current temperature and whether the
heater is on or off.
SNMP MIB Point
Data
atiMgmtSysTempStatus (1.3.6.1.4.1.926.1.3.2.4.2)
Temperature device ON or OFF
atiBBSysViewBatteryTemperature (1.3.6.1.4.1.926.1.4.1.1.3.5)
Battery temperature (in degrees C)
7.9.12 Configuring the Battery Heater Mat Controller
In this example, values are written to their respective OIDs to set temperatures, control mode and
status reporting.
Table 7-7, Heater Mat OIDs and Functionality
Table 7-8, Heater Mat MIB Reports
7.9.11 Connecting the Battery Heater Mat Controller, continued