0 data management – Alpha Technologies DSM3 for XM2 - Technical Manual User Manual
Page 45

45
745-814-B8-001, Rev. C (03/2014)
6.2.1 SCTE-HMS Configurable Alarms, continued
Table 6-3, Recommended Settings for DSM3 Series Analog Alarms
Analog Alarms and Common Settings
Analog Alarms
Description
Alarm
Enable LOLO
LO
HI HIHI Deadband
psTotalStringVoltage
36V
Scaled representation of the full
battery string in 1/100 Volts units
0x0F
3300
3500
4520 4570 50
48V
0x0F
4400
4785
6030 6100 50
Individual Battery Voltage
Battery Voltage of 12V battery,
scaled 1/100 V
0x0F
1050
1150
1530 1550 20
psInputVoltage
120V
Scaled representation of the input
line voltage in 1/100 Volts units
0x0F
Varies by site. The XM2 will switch to standby at
nominal +15% -20%
220V
0x0F
psOutputVoltage
48V
Scaled representation of the
power supply output voltage in
1/100 Volts units.
0x0F
4300
4550
5050 5300 200
60V
0x0F
5650
6000
6600 7000 200
90V
0x0F
7800
8200
9150 9300 200
psPowerOut
Representation of power supply
output power in 1W units.
0x00
It is recommended that psOutputCurrent be used
for output alarms.
psStringChargeCurrent
Battery string charge current,
scaled in 1/100 Amp units.
0x0C
Disable Disable 1200 1250 20
psStringFloat
Battery string float charge current,
scaled in 1/100 Amp units.
0x0C
Disable Disable 1200 1250 20
psOutputCurrent
15A
Scaled representation of power
supply RMS current in 1/100 Amp
units.
0x0C
Disable Disable 1650 1720 20
18A
0x0C
Disable Disable 1980 2060 20
22A
0x0C
Disable Disable 2420 2530 40
24A
0x0C
Disable Disable 2640 2750 40
psTemperature
-40 to +80 degrees C
0x0F
Varies by site
docsIfDownChannelPower
The CM's receive RF power
scaled in 1/10 dBmV units
0x0F
-150
-10
10
150
15
docsIfCmStatusTxPower
The CM's transmit RF power
scaled in 1/10 dBmV units
0x0C
0
0
500
550
15
Alarms for Optional Generator
GenVBatIgnition
Scaled representation of the
generator's ignition battery in
1/100 Volts
0x0F
1150
1200
1500 1550 20
genEnclosureTemperature
Temperature inside generator's
enclosure in degrees C
0x09
-40
0
0
55
5
The following table displays the various analog alarms with common settings for the DSM3 Series
Communications Module.
6.0 Data Management
Analog Alarms and Common Settings, DPM
Analog Alarms
Description
Alarm
Enable LOLO
LO
HI HIHI Deadband
psInputVoltage
120V
Scaled representation of the input
line voltage in 1/100 Volts units
0x0F
Varies by site. The XM2-300HP will switch to
standby at nominal +10% -15%
220V
0x0F
psOutputVoltage
60V
Scaled representation of the
power supply output voltage in
1/100 Volts units.
0x0F
5150
5350
6150 6350 200
63V
0x0F
5650
6000
6600 7000 200
90V
0x0F
7800
8200
9150 9300 200
psOutputCurrent
3.5A
Scaled representation of power
supply RMS current in 1/100 Amp
units.
0x0C
Disable Disable 380
390
20
5.0A
0x0C
Disable Disable 550
575
20
The following table displays analog alarms with common settings for the DPM Communications
Module that differ from the DSM3 Series models.
Table 6-4, Recommended Settings for DPM Analog Alarms