beautypg.com

Alpha Technologies Cordex 48-1kW 19 6000W User Manual

Page 46

background image

c 2004 ARGUS TECHNOLOGIES

CAN TERMINATED

JUMPER SETTING FOR P1

CAN UNTERMINATED

DIMENSIONS ARE IN INCHES WITH METRIC (mm) IN BRACKETS: INCHES [mm]

SIZE

DWG NO.

TYPE

B

SHEET

TITLE

ISSUE
DATE

OF

SCALE

FOR MANUFACTURING WITHOUT ITS WRITTEN CONSENT.

ARGUS TECHNOLOGIES AND SHALL NOT BE COPIED OR USED

THESE DESIGNS AND SPECIFICATIONS ARE THE PROPERTY OF

REV

030-707-08

C

D2

48-1kW CXRC 19" FLUSH MNT

3 4

CUSTOMER CONNECTION,

6 MOD OR 5 MOD w CXC SUP.

NTS

TB1

TB2

P1

J3

TB3

(REVERSIBLE)

AC INPUT KNOCKOUT PLATE

AC INPUTS

ACCEPTS 3/4" FITTING/CONDUIT

1.125" KO

ACCEPTS 1/2" FITTING/CONDUIT

#1/4-20 CHASSIS GROUND

0.875" KO

DC OUTPUT

E2 COMMON (+)

LIST 0,9,82 - 6 MODULE ,THREE FEEDS

TIGHTEN TO 8 FT-LB

)

J4

USES 1/4-20 x 5/8" OUTPUT LUGS

E1 LIVE ( -

#6-32 SCREWS

L2/N

TB3 FEEDS RECTIFIERS 5, 6

TB2

TYPICAL AC INPUT TERMINAL BLOCK

(TB2 SHOWN)

TB1 FEEDS RECITIFIERS 1, 2

TB2 FEEDS RECTIFIERS 3, 4

L1

1. GND

J3

J4

P1

2. CAN H

CAN IN RJ12 OFFSET

PIN OUT (J4)

6. NOT CONNECTED

4. CAN L
5. NOT CONNECTED

3. NOT CONNECTED

PIN OUT (J3)

CAN OUT RJ12 OFFSET

1. GND
2. CAN H
3. NOT CONNECTED
4. CAN L
5. NOT CONNECTED
6. NOT CONNECTED