Alpha Technologies Continuity: 1000_2000_3000 User Manual
Page 40

0170009-J0 Rev B
38
Protection
Overload
(AC Mode )
<105% continuous
>106%~120% for 30 sec transfer to bypass
>121%~150% for 10 sec transfer to bypass
>150% for immediate transfer to bypass
Buzzer continuously alarms.
(Battery Mode)
<105% continuous
>106%~120% for 30 sec shut down
>121%~150% for 10 sec shut down
>150% for immediate shut down
Buzzer continuously alarms.
(Bypass Mode)
<105% continuous
>106%~120% for 250 sec shut down
>121%~130% for 125 sec shut down
>131%~135% for 50 sec shut down
>136%~145% for 20 sec shut down
>146%~148% for 5 sec shut down
>149%~157% for 2 sec shut down
>158%~176% for 1 sec shut down
>177%~187% for 0.32 sec shut down
>188% for 0.16 sec shut down
Buzzer continuously alarms.
Short Circuit
Bypass mode : Input Fuse/Input Breaker
Normal Mode: Output Breaker/Electronic Circuit
Battery Mode: Output Breaker/Electronic Circuit
Battery
ABDM
EPO
UPS shuts down immediately
Over Temperature
Normal Mode
Transfer to Bypass Mode
Battery Mode
UPS shuts down immediately
Audible Alarm
Battery Mode
Sounding once every 1.5 sec
Low Battery
Sounding once every 0.2 sec
Overload
Sounding once every 3 sec
Fault
Continuously Sounding (or Sounding once every 3 second)
Environmental
Operating Temperature
+32°F to + 104°C (0°C to + 40°C)
Storage Temperature
+5°F to + 104°F (-15°C to + 40°C)
Relative Humidity
0% to 90%, non-condensing
Noise Level
<50dBA