Alpha Technologies Continuity: 1000_2000_3000 User Manual
Page 39

37
0170009-J0 Rev B
Output
Output -
INV mode
Voltage
115V
115V, adjustable to 100/110/115/120/127
230V
230V, adjustable to 200/208/220/230/240
Voltage Regulation
≤ ± 1% until low battery warning
Frequency(Synchronized
Range)
3Hz or 1Hz (setting by software)
Frequency(Battery Mode)
±0.1% (0.05~0.06Hz) unless synchronized to line
Current
Crest Factor
PF=0.8
2.7:1
Harmonic Distortion
1KVA,2KVA, 3KVA ≤ 3% THD(Linear Load)
1.5KVA ≤ 4% THD(Linear Load)
≤ 7% THD(Non-Linear Load)
Transient Response (ms)
≤ 60ms/±5%
Waveform
Pure sine wave
Efficiency
To AC Mode (Full load)
85%
85%
88%
To Battery Mode (Full load) 83%
83%
85%
Battery Parameters
Model number
AIDCO 1 kVA
AIDCO 2 kVA
AIDCO 3 kVA
Type
12V/7.2Ah
12V/7.2Ah
12V/9Ah
Number of Batteries
3
6
6
Backup Time (Full Load)
PF=0.8
>5min.
>5min.
>4min.
Recharging Time
4 Hours to 90%
Charging Current (Max.)
1.8A
2.16A
2.7A
Charging Voltage
41.0Vdc ±0.5V
82.0VDC ±0.5V
82.0VDC ±0.5V
Hot Swappable Battery
Yes
Internal battery
Yes
DC leakage current
≤ 30uA (±10uA) with no AC applied and the unit in the off
position
Battery type
Sealed, non-spill, maintenance-free, lead acid
Transfer Time
AC to DC
Zero
Inverter to Bypass
2.5ms (Typical)
Zero
DC Start
Yes
Self Diagnostics
By button on the panel or Software Control
Front Panel
LED
Load Level/Battery Level/ Battery Mode/ Normal Mode/
Bypass Mode/ Self-Test/ Weak/Bad Battery/Site Wiring Fault/
Fault/ Overload/Programmable Outlet1//Programmable
Outlet2
Key
ON Button/ OFF Button/ (Test/Alarm Reset Button)