beautypg.com

4 repo switch – Alpha Technologies Continuity: 1000_2000_3000 User Manual

Page 22

background image

0170009-J0 Rev B

20

4.4  REPO Switch

The UPS is equipped with a remote emergency power off (REPO) switch. The user must supply a means

of interfacing with the REPO circuit so that the UPS input feeder breaker can be switched off to interrupt

all sources of power to the UPS and connected equipment. This requirement complies with national and

local wiring codes and regulations.

1 = REPO+
2 = Ground
Short Pin 1 and Pin 2 to enable the REPO function

1

2