3.8  Communication Ports

The UPS is equipped with a remote emergency power off (REPO) dry contact input, true RS232 and

USB communication ports to provide communication with bundled UPS monitoring software for remote

monitoring of UPS status via a PC.
Four optional interface cards are available to meet various communication needs (Refer to Section 7):
• DCE (dry contact relay card)
• RS232
• USB
• SNMP/WEB card
The bundled software of the UPS is compatible with many operating systems such as Windows 98, 2000,

ME, NT and XP. For other applications such as Novell, NetWare, Unix, Linux, please contact your local

dealer for suitable software.
All communication ports (including optional cards) can be active simultaneously to monitor the UPS sta-

tus. However only 1 communication interface can be active at any one time. The interface with the high-

est priority controls the UPS. The priority of these communication interfaces are as follows from highest to

lowest priority:
• EPO input port
• Optional Interface card
• USB
• RS232

3.8.1  RS232 Port Settings

Set the RS232 interface as follows:

Baud Rate:

2400 bps

Data Length:

8 bits

Stop Bit:

1 bit

Parity:

None

3.8.2  USB Port Descriptions

The USB communication protocol definition complies with:
• USB version 1.0, 1.5Mbps
• USB HID Version 1.0.