beautypg.com

4 wiring – ABUS SG1810 Profiline sounder User Manual

Page 16

background image

16

6.4 Wiring

Terminal

Description

LED

Connector for LED2. The LED lights up for a negative
trigger signal (0 V DC at input).

AUX RED
COM BLK

Standard connections for power supply (13.8 V
DC/200 mA max.).

BUS YEL / BUS GRN

Not used.

SPEAKER

Connections for the sounder speaker (8 Ohm,
30 W).

BLK
RED

Connections for the backup power supply (12 V/2.1
Ah).
The battery is charged automatically by the auto-
recharging battery circuit.

PS +
PS -

Optional connections for power supply (13.8 V DC/
1.6 A).

IMPORTANT:

If you use a battery, there is no need to connect these
terminals!

These connections are required if you do not want to
use a battery.
The maximum current from these connections is 1.6
A. The AUX RED and COM BLK connections can be
left free.

IMPORTANT:

Make sure that the power source supplies the
necessary current of 1.6 A; otherwise, the alarm
system cannot work correctly!
Note that the compact alarm has no backup power
supply if connected like this!

TAMPER R
TAMPER F

JP3 (PCB)

Tamper connections for wall and cover contact. The
connection of the contacts depends on the TAMPER
jumper.
The tamper contacts are connected to the JP3 pins.

PROX (N.C)

Not used.

TRBL (N.O)

The reaction of the trouble output depends on the
setting of the dip-switch (CONFIG 1).

C+

-

Connected to +12 V »»» sounder is off

-

Loss of +12 V signal (or switch to
0 V) »»» sounder is activated

This manual is related to the following products: