TROUBLESHOOTING
If trouble is experienced with the operation of the valve, it usually
falls into one of the following categories:

SYMPTOM

PROBABLE CAUSE

CORRECTIVE
ACTION

Valve leaks, will

1) Trash caught

Remove valve,

not close drip tight. between tube

clean.

& barrier.

2) Tube diaphragm

Remove valve,

failure. (very unlikely

replace tube

possibility)

diaphragm.

Valve will not

1) Strainer plugged

Remove strainer

open, close or

screen and

operates clean.
sluggishly.

2) Dirt in control

Remove,

system or valve

clean trim and

trim orifice.

orifice.

3) Dirt in pilot

Remove pilot,

valve

inspect and
clean. See
specific pilot
instructions.

4) Dirt in solenoid

Remove SOV,

valve or incorrect

inspect and

voltage

clean. Verify
correct voltage
to coil.

Pipes move, bang

1) Water hammer and/ May require

or rattle

or hydraulic surge

system hydraulic
analysis.

2) Valve operating

Change closing

too fast

speed orifice
in control
tubing, or
install opening
speed orifice
in pilot
exhaust.