Purchase specifications, Dimensions, Flow chart – Cla-Val 50B-5KG User Manual

Page 5: Cla-val

background image

1
2
3
4
5
6

100KCGVX Hytrol (Main Valve)
CRL5A Pressure Relief Control
X44A Strainer and Orifice Assembly
CV Flow Control (Opening)
X101C Valve Position Indicator
CK2 (Blow-Off Valve)

Purchase Specifications

The Fire Pump Suction Control Valve shall modulate to main-
tain a minimum pressure at the pump suction regardless of
system demand. It shall control the pump discharge in rela-
tion to the suction head available, and shall not allow suction
head pressure to fall below a pre-set minimum.

It shall be actuated by line pressure through a pilot control sys-
tem which allows rapid response to changing pressure condi-
tions without line surges. The pilot control shall be remote
sensed to the pump suction head pressure.

The main valve shall be of the hydraulically-operated, pilot-
controlled, diaphragm-type, globe or angle valve. It shall have
a single removable seat, a delrin-sleeved guided stem and a
renewable resilient synthetic rubber disc with a rectangular
cross section, contained on three and one-half sides by a disc

retainer and disc guide. No external packing glands shall be
permitted and the diaphragm shall not be used as a seating
surface. The pilot control shall be a direct-acting, adjustable,
spring-loaded, diaphragm-type valve designed for modulating
service to permit flow when controlling pressure exceeds
spring setting.

A device indicating the percent at which the valve is open or
closed shall be supplied on the assembly, together with a sed-
iment evacuator and dampening device.

The valve shall be designed to allow for repair and servicing
without removing the valve body from the line.

The valve shall be Factory Mutual Approved. It shall be the
MODEL 50B-5KG FIRE PUMP SUCTION CONTROL VALVE
as manufactured by Cla-Val, Newport Beach, California.

4

OPENING SPEED CONTROL ADJUSTMENT:
TURN THE ADJUSTING SCREW CLOCKWISE TO
MAKE THE MAIN VALVE OPEN SLOWER.

3

G

F

(MAX.)

5

E

(MAX.)

K

6

1

2

PRESSURE RELIEF CONTROL ADJUSTMENT:
TURN THE ADJUSTING STEM CLOCKWISE TO
INCREASE THE SETTING.

REMOTE SENSING LINE CONNECTION:
1/8" - 27 N.P.T.

OUTLET

CC

C

BB

B

AA

INLET (ANGLE PATTERN)

(4" SIZE VALVE SHOWN)

INLET

DD

D

A

Flow - Gallons Per Minute

P

re

s

s

u

re

D

ro

p

-

p

s

i

Dimensions

(

in Inches)

Flow Chart

VALVE

SIZE

AA

300 LB.

FLANGES

A

150 LB.

FLANGES

B

150 LB.

FLANGES

CC

300 LB.

FLANGES

C

150 LB.

FLANGES

DD

(TYP.)

300 LB.

FLANGES

(MIN.)

D

(TYP.)

150 LB.

FLANGES

(MIN.)

E

(MAX.)

F

(MAX.)

G

(MAX.)

K

BB

300 LB.

FLANGES

3”
4”
6”
8”

13.25
15.62
21.00
26.38

12.00
15.00
20.00
25.38

6.00
7.50

10.00
12.75

4.38
5.31
6.50
8.50

4.00
5.00
6.00
8.00

1.12
1.25
1.44
1.62

.75
.94

1.00
1.12

15.75
17.75
20.25
23.00

13.50
15.00
16.50
20.00

4.62
5.75
7.88

10.00

2.56
3.19
4.31
5.31

6.38
7.88

10.50
13.25

PO Box 1325 Newport Beach CA 92659-0325 Phone: 949-722-4800
Fax: 949-548-5441

Web Site: cla-val.com

E-mail: [email protected]

CLA-VAL

CLA-VAL CANADA

CLA-VAL EUROPE

4687 Christie Drive
Beamsville, Ontario
Canada LOR 1B4
Phone: 905-563-4963
Fax: 905-563-4040
E-Mail: [email protected]

Chemin des M

;

sanges 1

CH-1032 Romanel/
Lausanne, Switzerland
Phone: 41-21-643-15-55
Fax: 41-21-643-15-50
E-Mail: [email protected]

'COPYRIGHT

CLA-VAL 2002 Printed in USA Specifications subject to change without notice.

CLA-VAL UK

Dainton House, Goods Station Road
GB - Tunbridge Wells
Kent TN1 2 DH England
Phone: 44-1892-514-400
Fax: 44-1892-543-423
E-Mail: [email protected]

Represented By:

50B-5KG (R-11/06)

Item

No.

Description