beautypg.com

50b-5kg, Pump suction control valve, Typical installation – Cla-Val 50B-5KG User Manual

Page 4: Specifications, Model

background image

50B-5KG

• Adjustable Opening Speed For Pump Suction

Protection

• Pilot Control Provides Wide Flow Range With

Minimal Pressure Variations

• Controlled Closing For System Protection

• Modulates Within 5% of Setting for Accurate

Pressure Control

• Pressure Setting Adjustable

• Pressure Setting Not Affected by Pressure at Valve

Discharge

The Model 50B-5KG Pump Suction Control Valve is
designed specifically for Fire Pump Suction Control Service.
It modulates to maintain the pump discharge in relation to
the suction head available, thus assuring that the suction
head pressure does not fall below the pre-set minimum.

Pump Suction Control Valve

Typical Installation

When there is a demand in the Fire System, the pump is started,
delivering water from the supply source to the area of demand. To
assure that the fire pump draw does not exceed the available water
supply, the Model 50B-5KG, sensing the pump suction, modulates
to prevent suction pressure from dropping below a pre-set minimum.

By maintaining minimum pressure requirements in the supply main,
the main is protected from possible damage or backflow conditions.
Also, a minimum supply pressure is provided for local fire apparatus.

Specifications

Globe: 3" - 8" flanged
Angle: 3" - 8" flanged

150 and 300 ANSI B16.42

150 class - 250 psi Max.
300 class - 400 psi Max

Water, to +180°F Max.

Main valve body & cover
Ductile Iron ASTM A-536

Main valve trim:
Brass QQ-B-626
Bronze Seat ASTM B61
Stainless Steel Stem 303
Delrin Sleeved

Pilot control system:
Cast Bronze ASTM B62 with
303 Stainless Steel trim

Available in the following
pressure range only:
5 to 25 psi
Set at 10 psi

Sizes

End Details

Pressure Ratings

Temperature Range

Materials

Adjustment Range

TO

FIRE SERVICE

SYSTEM

REMOTE SENSING LINE

CLA-VAL 50B-5KG

FIRE PUMP

SUPPLY SYSTEM

50B-5KG