Cla-val, Ee d e, Dd aa – Cla-Val 100-22 600 Series User Manual
Page 4: Fa c, Kj h, Ff b

CLA-VAL
Copyright Cla-Val 2013 Printed in USA Specifications subject to change without notice.
P.O. Box 1325
• Newport Beach, CA 92659-0325 • Phone: 949-722-4800 • Fax: 949-548-5441 • E-mail: [email protected] • Website cla-val.com
©
Cla-Val Control Valves operate with maximum efficiency when mounted in horizontal piping with the main valve cover UP, however, other posi-
tions are acceptable. Due to component size and weight of 10 inch and larger valves, installation with cover UP is advisable. We recommend
isolation valves be installed on inlet and outlet for maintenance. Adequate space above and around the valve for service personnel should be
considered essential. A regular maintenance program should be established based on the specific application data. However, we recommend a
thorough inspection be done at least once a year. Consult factory for specific recommendations.
E-100-22 (R-2/2013)
EE
D
E
Inlet
DD
AA
100-22
Flanged
F
A
C
(MAX)
K
J
H
Inlet
Outlet
FF
B
(Diameter)
Model 100-22
Dimensions
Valve Size
(Inches)
4
6
8
10
12
14
16
18
20
24
A 150 ANSI
13.88
17.75
21.38
26.00
30.00
34.25
35.00
42.12
48.00
48.00
AA 300 ANSI
14.50
18.62
22.38
27.38
31.50
35.75
36.62
43.62
49.62
49.75
B Dia.
9.12
11.50
15.75
20.00
23.62
28.00
28.00
35.44
35.44
35.44
C Max.
11.75
15.25
20.25
23.75
27.25
29.31
34.12
35.00
40.25
40.25
D 150 ANSI
6.94
8.88
10.69
—
—
—
—
—
—
—
DD 300 ANSI
7.25
9.38
11.19
—
—
—
—
—
—
—
E 150 ANSI
5.50
6.75
7.25
—
—
—
—
—
—
—
EE 300 ANSI
5.81
7.25
7.75
—
—
—
—
—
—
—
F 150 ANSI
4.50
5.50
6.75
8.00
9.50
11.00
11.75
15.88
14.56
17.00
FF 300 ANSI
5.00
6.25
7.50
8.75
10.25
—
12.75
15.88
16.06
19.00
H NPT Body Tapping
.50
.75
.75
1
1
1
1
1
1
1
J NPT Cover Center Plug
.50
.75
.75
1
1
1.25
1.25
2
2
2
K NPT Cover Tapping
.50
.75
.75
1
1
1
1
1
1
1
Valve Stem Internal
Thread UNF
1
⁄
4
-28
1
⁄
4
-28
3
⁄
8
-24
3
⁄
8
-24
3
⁄
8
-24
3
⁄
8
-24
3
⁄
8
-24
1
⁄
2
-20
1
⁄
2
-20
1
⁄
2
-20
Stem Travel
0.8
1.1
1.7
2.3
2.8
3.4
3.4
4.5
4.5
4.5
Approx. Ship Wt. Lbs.
135
230
480
785
1410
2215
2215
2300
3400
3600
Valve Size
(mm)
100
150
200
250
300
350
400
450
500
600
A 150 ANSI
353
451
543
660
762
870
889
1070
1219
1219
AA 300 ANSI
368
473
568
695
800
—
930
1108
1260
1263
B Dia.
232
292
400
508
600
711
711
900
900
900
C Max.
298
387
514
603
692
744
867
889
1022
1022
D 150 ANSI
176
226
272
—
—
—
—
—
—
—
DD 300 ANSI
184
238
284
—
—
—
—
—
—
—
E 150 ANSI
140
171
184
—
—
—
—
—
—
—
EE 300 ANSI
148
184
197
—
—
—
—
—
—
—
F 150 ANSI
114
140
171
203
241
279
298
403
370
432
FF 300 ANSI
127
159
191
222
260
—
324
403
408
483
H NPT Body Tapping
.50
.75
.75
1
1
1
1
1
1
1
J NPT Cover Center Plug
.50
.75
.75
1
1
1.25
1.25
2
2
2
K NPT Cover Tapping
.50
.75
.75
1
1
1
1
1
1
1
Valve Stem Internal
Thread UNF
1
⁄
4
-28
1
⁄
4
-28
3
⁄
8
-24
3
⁄
8
-24
3
⁄
8
-24
3
⁄
8
-24
3
⁄
8
-24
1
⁄
2
-20
1
⁄
2
-20
1
⁄
2
-20
Stem Travel
20
28
43
58
71
86
86
86
114
114
Approx. Ship Wt. Kgs.
61
104
218
356
640
1006
1006
1044
1544
1634