Cla-Val 133-01/633-01 User Manual
Page 8

5 RSP: HIGH
Defines highest SP value from a remote source
Set to high RSP value
Optional - Can be any value
6 TRACKING
Defines whether the local setpoint will track the RSP
Yes
7 BIAS LOW
Defines the lowest bias value that may be entered
Minus 1000
8 BIAS HIGH
Defines the highest bias value that may be entered
Plus 1000
9 RSP FIXED
Defines control mode when a RSP signal is restored
Remote SP
RETRANS.
Parameter
Description
Values
Comments
1 TYPE: 3
Defines what signal is to be transmitted
PV
Optional - Other inputs available
2 LOW RANGE
Defines low end range
Set to low PV value
3 HIGH RANGE
Defines high end range
Set to high PV value
SELF TUNE
- NOT USED -
SPECIAL
Parameter
Description
Values
Comments
1 AUTO.TRIP
Defines the automatic trip function
Off
1 DES. OUTPT.
Not applicable
Last out
3 POWER UP
Defines the control mode upon power up
Last mode
4 PWR. UP: OUT
Not applicable
Last Out
5 PWR. UP: SP
Defines the setpoint upon power up
Last SP
6 NO. OF SP
Defines the number of local setpoints
1
SECURITY
If used - See page 48
SER. COMM.
If used - See page 49
TUNING
Parameter
Description
Values
Comments
1 POWR. BACK
Reduces setpoint overshoot at power up
Disabled
2 PROP. BND: 1
Defines the proportional band for the first output
50%
Lower for faster valve response
Higher for slower valve response
3 MAN. RST: 1
Specifies the load line out value
50%
Always use this value
4 CYCLE TM: 1
Defines the cycle time for the first output
10 Seconds
Lower for faster valve response
Higher for slower valve response
5 CTRL. D.B.
Not used
0
6 PID OFST: 1
Defines the deadband above the setpoint
0
Optional - Positive number
7 PID OFST: 2
Defines the deadband below the setpoint
0
Optional - Negative number
8 REL. GAIN: 2
Defines the adjustment factor for the output 2
1
proportional band. It is a ratio of the proportional
band of the first output
9 CYCLE TM: 2
Defines the cycle time for the second output
10 Seconds
Lower for faster valve response
Higher for slower valve response
10 NO. OF PID
Defines the number of PID loops
1
11 TOTALIZER
Disables or enables totalizer function
User Defined
12 TTL. DECML
Defines position of decimal point
User Defined
13 TTL.SCALE
Defines whether thousands (KGL) or millions (MGL) of gallons volume
User Defined
KGL or MGL
14 TTL.RESET
Defines whether totalizer recycles (Auto) or stops (Manual) at limit
User Defined
if Manual press down arrow to reset
15 TTL.LIMIT
Establishes totalizer upper limit
0 to 99999