5 RSP: HIGH

Defines highest SP value from a remote source

Set to high RSP value

Optional - Can be any value

6 TRACKING

Defines whether the local setpoint will track the RSP

Yes

7 BIAS LOW

Defines the lowest bias value that may be entered

Minus 1000

8 BIAS HIGH

Defines the highest bias value that may be entered

Plus 1000

9 RSP FIXED

Defines control mode when a RSP signal is restored

Remote SP

RETRANS.
Parameter

Description

Values

Comments

1 TYPE: 3

Defines what signal is to be transmitted

PV

Optional - Other inputs available

2 LOW RANGE

Defines low end range

Set to low PV value

3 HIGH RANGE

Defines high end range

Set to high PV value

SELF TUNE

- NOT USED -

SPECIAL
Parameter

Description

Values

Comments

1 AUTO.TRIP

Defines the automatic trip function

Off

1 DES. OUTPT.

Not applicable

Last out

3 POWER UP

Defines the control mode upon power up

Last mode

4 PWR. UP: OUT

Not applicable

Last Out

5 PWR. UP: SP

Defines the setpoint upon power up

Last SP

6 NO. OF SP

Defines the number of local setpoints

1

SECURITY

If used - See page 48

SER. COMM.

If used - See page 49

TUNING
Parameter

Description

Values

Comments

1 POWR. BACK

Reduces setpoint overshoot at power up

Disabled

2 PROP. BND: 1

Defines the proportional band for the first output

50%

Lower for faster valve response
Higher for slower valve response

3 MAN. RST: 1

Specifies the load line out value

50%

Always use this value

4 CYCLE TM: 1

Defines the cycle time for the first output

10 Seconds

Lower for faster valve response
Higher for slower valve response

5 CTRL. D.B.

Not used

0

6 PID OFST: 1

Defines the deadband above the setpoint

0

Optional - Positive number

7 PID OFST: 2

Defines the deadband below the setpoint

0

Optional - Negative number

8 REL. GAIN: 2

Defines the adjustment factor for the output 2

1

proportional band. It is a ratio of the proportional
band of the first output

9 CYCLE TM: 2

Defines the cycle time for the second output

10 Seconds

Lower for faster valve response
Higher for slower valve response

10 NO. OF PID

Defines the number of PID loops

1

11 TOTALIZER

Disables or enables totalizer function

User Defined

12 TTL. DECML

Defines position of decimal point

User Defined

13 TTL.SCALE

Defines whether thousands (KGL) or millions (MGL) of gallons volume

User Defined

KGL or MGL

14 TTL.RESET

Defines whether totalizer recycles (Auto) or stops (Manual) at limit

User Defined

if Manual press down arrow to reset

15 TTL.LIMIT

Establishes totalizer upper limit

0 to 99999