CONFIGURATION
Parameter

Description

Values

Comments

1 SENS. LOC.

Select DP sensor location Valve(=Default) or Pipe

Valve or Pipe

Factory DP sensor is across valve, select pipe if mounted on pipe

2 VALVE TYP.

Selects size and type of valve

User Defined

3 FLOW:UNITS

Selects GPM or LPM

User Defined

4 SPEC. GRAV.

Selects specific gravity of product

1.00 for water

5 LINE FREQ.

Electrical frequency

50 or 60 HZ

6 REM. SETPT.

Selects the remote setpoint option

Enabled or Disabled

Select one

7 OUTPUT 3

Defines the function of the third optional output

Retransmission

8 ANLG. RNG: 3

Defines the output signal for retransmission

4-20mA

RSP INPUT

Disables or enables remote setpoint

User Defined

9 LOOP NAME

A 9-character message associated with the loop

User Defined

CONTROL
Parameter

Description

Values

Comments

1 ALGORITHM

Defines the type of control algorithm

P

2 ACTION: 1

Defines the action of the first control output

Reverse

3 FIXED LAG

Defines lag between control iterations

0

4 LOW OUT

Defines the low output level

0%

5 HIGH OUT

Defines the high output level

100%

6 ACTION: 2

Defines the action of the second control output

Direct

VPOS INPUT

Valve position input

Parameter

Description

Values

Comments

1 PV TYPE

Specifies the PV input type and range

4-20mA

2 DECIMAL

Specifies the decimal point position

Fixed

3 LINEARIZE

Specifies if the PV input is to be linearized

None

4 LOW RANGE

Specifies value corresponding to the low PV input

0

5 HIGH RANGE

Specifies value corresponding to the high PV input

100

6 FILTER

Setting to stabilize input signal

2 sec.

Optional - Can be any value for filtering signal

7 PV OFFSET

Defines the offset to the PV signal

0

Optional - Offset as required to match PV signal

8 PV GAIN

Defines the gain to the PV signal as a ratio

1

Optional - Gain as required to match PV signal

9 VPOS BREAK

Defines valve position if PV signal is lost

25%

Valve closes - Opens if used for back pressure control

50%

Valve remains in same position

75%

Valve opens - Closes if used for back pressure control

10 VP REST.

Defines control mode when a PV signal is restored

Last mode

DPRS. INPT.

Differential pressure input

Parameter

Description

Values

Comments

1 PV TYPE

Specifies the PV input type and range

4-20mA

2 DECIMAL

Specifies the decimal point position

Fixed

4 LOW RANGE

Specifies value corresponding to the low PV input

User defined

Low span of transmitter

5 HIGH RANGE

Specifies value corresponding to the high PV input

User defined

High spen of transmitter

6 FILTER

Setting to stabilize input signal

2 sec.

Optional - Can be any value for filtering signal

7 PV OFFSET

Defines the offset to the PV signal

0

Optional - Offset as required to match PV signal

8 PV GAIN

Defines the gain to the PV signal as a ratio

1

Optional - Gain as required to match PV signal

9 DPRS. BRK.

Defines valve position if PV signal is lost

25%

Valve closes - Opens if used for back pressure control

50%

Valve remains in same position

75%

Valve opens - Closes if used for back pressure control

10 DPRS. REST.

Defines control mode when a PV signal is restored

Last mode

SETPOINT
Parameter

Description

Values

Comments

1 SP LOW

Specifies low span for local setpoint

0

2 SP HIGH

Specifies high span for local setpoint

User defined

Usually equal to flow at 20 FPS

3 SP RAMP

Defines the rate of change for setpoint changes

0

ALARMS
Parameter

Description

Values

Comments

1 ALM. TYPE: 1

Defines the type of alarm for alarm 1

Off

If using alarms - see alarm section

2 ALM. TYPE: 2

Defines the type of alarm for alarm 2

Off

If using alarms - see alarm section

REM. SETPT.
Parameter

Description

Values

Comments

1 TYPE V/mA

Specifies the type of remote setpoint output signal

1-5 / 4-20

2 RSP: LO RNG.

Specifies value corresponding to the low RSP input

Set to low RSP value

3 RSP: HI RNG.

Specifies value corresponding to the high RSP input

Set to high RSP value

4 RSP: LOW

Defines the lowest SP value from a remote source

Set to low RSP value

Optional - Can be any value

TYPICAL 131VC-3T CONTROLLER PARAMETER SETTINGS