Product Type
K. Kit to install on existing valve
N. Install on a new valve
Main Valve Selection
Valve Size
Indicate valve size 2” thru 24”
Valve Type
F. Full port
R. Reduced port
Valve Pattern
G. Globe pattern
A. Angle pattern
Valve Trim
S. Standard
A. Anti-Cavitation
Component Selection
131VF Module Mounting
D. DIN rail (Standard)
V. Valve mount
N. None
Sensor Type
D. DP transmitter (qty 1)
P. Pressure transmitters (qty 2)
N. None
Tubing & Fittings for DP Sensor
C. Copper (Standard)
S. Stainless Steel
(Three CK2 isolation valves included)
Sensor Mounting
L. Left side (Standard)
R. Right side
N. None
X117D Position Transmitter
Options
N. None (Already installed)
O. with One limit switch
T. with Two limit switches
Special Options
N. None
KX. KX
denotes extra or special configurations not listed above.
Contact your local Cla-Val representative for assistance.
C L A - V A L 1 3 3 V F S y s t e m O r d e r i n g
M o d e l N u m b e r 1 3 3 V F -
}
}
}
}
}
}
}
}
}
}
}
CLA-VAL
4687 Christie Drive
Beamsville, Ontario • Canada L0R 1B4
Ph: 905-563-4963 • Fax: 905-563-4040 • www.cla-val.ca
CLA-VAL CANADA
CLA-VAL EUROPE
Chemin des Mesanges 1
CH-1032 Romanel/Lausanne, Switzerland • www.cla-val.ch
Ph: 41-21-643-15-55 • Fax: 41-21-643-15-50
PO Box 1325 Newport Beach, CA 92659-0325 • www.cla-val.com • Ph: 949-722-4800 • Fax: 949-548-5441
131VF Specifications
Enclosure:
2” x 3” x 4”, Non-Metallic
IP-68 Rated
Power Requirement:
24VDC, 150 mA
Flow Signal Output:
4-20 mA analog unpowered
System Total Power Requirement: 24VDC, 500 mA
Accuracy and Calibration Recommendations
All sensors must be calibrated for best accuracy. In addition, the differential
pressure transmitter must be set to the correct range. Typical accuracy is
within 2 to 3% actual flow. Accuracy may be less than this if:
• Valve position is less than 5%
• Sensors are not calibrated or zeroed
• Incorrect range of differential pressure transmitter
• Valve is corroded
• Inlet & outlet are not full pipe flow
• Valve pressure differential less than 1 psid
For new valves, please specify with the
“KVF” suffix letters plus the 133VF
model number added after valve model
number.
Example:
90-01BY KVF - 133VF-N-6FGS-VPCLNN
valve
model #
133VF model #
E-133VF (R-9/2011)
When ordering133VF system, in
addition to model number specify:
1. Analog output signal flow scale (i.e. -
Output Flow: 0 to 1000 GPM). Must be
suitable to valve capacity and system
capabilities.
2. Input pressure sensor type (DPT or
P1-P2) and full scale output @20mA
(P1 and P2 must have same scale.)
Note: Cla-Val supplied DPT have
standard scale of 0 to 100 psid.