CONTROL VARIATIONS – Models PZi8 & PZiG

Multi-liquid Proportional Flow Rate
Injection – Models PZi8* & PZiG

Multiple PZiGs inject different chemicals according to preset
values while calculating the signal from a single flow meter.
This eliminates the need for a signal distributor.

Advantage

2-point Level Switch-based Control
– Models PZi8 & PZiG

A 2-point level control enables output of an alarm at
the liquid level “low limit” and stops pump operation at
the “low-low limit.”

Advantage

Batch Injection (counter)*
– Models PZi8 & PZiG

Pump operation starts on command signal. Operation auto-
matically stops and operator is notified of completion when
a preset count is reached. Maximum number of pulses 9999x1,
x10, x100 or x1000 (555 hours max. run time).**

Advantage

Interval Injection (repeat cycle)*
– Models PZi8 & PZiG

The pump is repeatedly started and stopped by a preset
timed program. ON time and OFF interval can be easily
set from 1 to 9999 minutes respectively.**

Advantage

PZiG

C

PZiG

B

PZiG

A

Flow meter
(pulse/analog)

Sodium

hydroxide

Sodium

hypochlorite

Polyaluminum

chloride

S

PZiG

system

P

PZiG

P

Alarm

PZiG

system

PZiG

F

Start signal

Discharge completed display

PZiG

system

PZiG

P

Stop signal

PZiG

system

P

Note:

Multiple PZiG pumps take pulse or analog signal directly: A single PZi8 pump would
take a pulse or analog signal directly and slave a second or third pump to its output.

*Input is

connected to
one PZi8 pump:
Multiple PZi4
pumps would
follow the pulse
output of the
PZi8 pump.

Adjustment range

Stroke speed

1~300 spm (1 spm step)

Stroke length adjustment

20~100%*

Analog input 4~20 mADC (110 ohm)

1

Number of inputs

Digital input high speed (125 Hz max.) Open collector

2

Digital input low speed (10 Hz max.) Open collector

2

Other

Power supply output +5VDC (10 mA max.)

1

LCD display

Display unit selection (%, mL, spm)

Manual operation

Manual mode

Analog mode

Analog signal

4~20 mADC

Pulse signal

1/ 1~1/ 9999

Automatic operation

Pulse signal

1 to 9999 times

Count mode

Number of strokes

1~9999 (x1, 10, 100, 1000)

Interval mode

ON/OFF time

1 to 9999 mins / 1 to 9999 mins

*50~100% for sizes -31/ -61/ -12

Stop input

Level switch input

Control input

Alarm reset input

Start/reset input

Operation signal output

Control output

Operation sync pulse output

1

End signal output

2

Analog input error alarm

3

Inpule pulse buffer overflow alarm

3

Alarm output

Level error alarm

3

Injection monitor error alarm

3

1. Output in sync with solenoid operation.
2. Output when operation for preset count is completed.
3. Alarm display, alarm output and pump operation can

be selected in response to an alarm condition.

B

as

ic

sp

ec

if

ic

at

io

ns

In

pu

ts

R

un

m

od

e

O

ut

pu

ts

*Calibration function assures accuracy greater than ordinary pumps in these applications (see page 3).

**Pump operation can be interrupted by a remote signal at any time; program resumes when restarted.