Vent terminal installation procedure – John Wood Noritz N-069M-DV User Manual
Page 63
63
1) Determine the vent terminal installation
location and make a 6.3" diameter hole.
Install the sleeve into the hole with the
triangular mark ( ) pointing up. Use the
wall anchors and rounded wood screws.
4.
Vent Terminal Installation Procedure
* When drilling, take care not to damage electric
wiring, or gas or water piping in walls.
6.85
5.6
5.6
6.85
Screw holes (4)
(0.3"diameter and
1.4"to 1.6"depth).
Triangular mark ( )
Before installing the sleeve, adjust its length to fit the
wall thickness.
(The length can be adjusted in increments of 0.4".)
Waterproof the clearance between the sleeve
and wall hole with a high temperature sealant.
2) Attach the wall flange to the sleeve.
Sleeve
Wall flange
Tapping screw
Terminal Orientation Flange Orientation
Outlet Orientation
(1)
The terminal cannot be installed in this
orientation.
Sleeve
Waterproof the
clearance with a high
temperature sealant.
Rounded wood screw (short)
Sleeve
Wall anchor
6.3" dia.
Waterproof the clearance with
a high temperature sealant.
Rounded wood
screw (long)
(2)
(4)
(3)
Up
Down
Up
Down
Top
Bottom
Correct
Correct
Incorrect
Incorrect
Intake
Exhaust
Intake
Exhaust
Up
Down
Up
Down
Intake
Exhaust
Intake
Exhaust
6.9"
8.3"
6.9"
8.3"
6.9"
8.3"
* The proper flange orientation
depends on the desired
orientation of the vent terminal.
* Unless the vent terminal is
installed as in option (1) in the
chart to the right, the outlet will
need to be adjusted in order to
ensure it is oriented in the proper
direction.
Remove this screw
and slide out the
external cylinder.
Slide out the external cylinder
until it is flush with the external
wall and replace screw.