Plumbing Applications

Pump Control Signal

See p. 53

(See p. 53)

(See notes for Sizing)

Pump Control Signal

See p. 53

Pump Control signal

See p. 53

Recirculation System

Pump

Fixtures

Cold Water Supply

NORITZ

N-069M-DV

Check

Valve

Hot Water Return

Check Valve

Pressure

Relief

Valve

Hot Water

Shutoff Valve

Drain

R

B

W

Use Honeywell Aquastat

(Model L6006A or L6006C)

Pump

AC120

Aquastat Wiring

105

Neutral

Ground

Live

5

Heating System

Cold Water Supply

NORITZ

N-069M-DV

Check

Valve

Hot Water Return

Pressure

Relief Valve

Hot Water

Shutoff Valve

Drain

Air Scoop
(Optional)

Temp. &

Press. Gauge

(Optional)

Hydronic Heat

Exchanger or

Radiant Heat

Piping

Pressure

Reducing

Valve

(Optional)

Shutoff

Valve

Backflow

Preventer

(Optional)

Boiler Drain Valve

Heating
Controls

Mixing Valve

N-069M-DV

Cold Water Supply

Tempered Potable Hot Water

Hot Water for Heating

If the system requires water
for space heating at a higher
temperature than for other
uses, means such as a mixing
valve shall be provided to
temper the water for the other
uses to help prevent scalding.

For Space Heating Purposes:

Check Valve

Aquastat

(Relay for

Pump

> 85 W)

(Use Aquastat if Unit

Isn't Controlling Pump)

Aquastat
(Use Aquastat if

Unit Isn't Controlling
Pump)

Pump

Pump Control Signal

See p. 53

Expansion Tank

(Install According

to Local Codes)

8-10 Gal.
Storage Tank
(To Alleviate Cold
Water Sandwich)

(See p. 53)

(Install According

to Local Codes)

(Relay for

Pump

> 85 W)

(See notes for Sizing)

Expansion

Tank

For Baseboard
Applications:
Please contact
Noritz for
compatibility.

* Size the pump to provide at least 2 GPM through the system at 10 Ft of Head plus
piping losses. Check the maintenance monitors on the unit to make sure the pump
is providing that much flow.
** Make sure that the flow rate is not greater than 4 ft/sec. (3/4”: 5 GPM, 1 1/4”: 13 GPM)

* Size the pump to provide at least 2 GPM through the system at 10 Ft of Head plus
piping losses. Check the maintenance monitors on the unit to make sure the pump
is providing that much flow.
** Make sure that the flow rate is not greater than 4 ft/sec. (3/4”: 5 GPM, 1 1/4”: 13 GPM)