beautypg.com

John Wood Superflue Power Vent (75 Gallon) User Manual

Page 31

background image

VII) COMBO HEATING

This section serves as a guide for the installation and use of
“Combo” heating systems utilizing a domestic water heater
that has been specifically approved for such use. It is writ-
ten for those knowledgeable in the required trades and pro-
fessionals involved in the design and installation of Combo
Heating Systems.
It is the responsibility of the installer/designer to follow
all applicable codes to ensure the effectiveness and
safety of the installation.

System Requirements

The following requirements must be met for the installation
of Combo Heating Systems:
1. All components used for the distribution of water in the

heating loop must be suitable for potable water. These
include all piping, fittings, solder and fluxes, pumps for
circulation of water, valves, etc.

2. The water heater must not be connected to a hydronic

heating system that has been used previously.

3. No boiler treatment chemicals of any kind shall be intro-

duced into the system.

4. The Combo System components must be selected and

sized to meet and maintain the total calculated
demands for both domestic service hot water and space
heating requirement. The sizing and installation must be
performed in accordance with good engineering prac-
tice such as “ASHRAE Handbooks”, HRAI,
“Hydronics Institute Manuals”, CGA B149, NFPA 54,
ANSI Z223.1, CSA F280, National/Provincial
Building Codes, CSA C22.1, ANSI/NFPA 70, CSA
B51
and/or codes having jurisdiction.

5. The air handler (fan coil) and/or the circulating pump in

a baseboard hydronic loop will require a dedicated
120V circuit. This must be provided and identified for
this purpose.

6. All piping between the water heater and the air handler

or hydronic baseboard loop must be adequately insulat-
ed to reduce heat loss.

7. If the local jurisdiction requires a back-flow preventer in

the cold water line, an expansion tank of adequate size
must be installed.

8. "Combo" Heating Systems require higher water temper-

atures than other applications. When the system is
used to supply water for Combo Heating applications, a
means, such as mixing valve, must be installed to tem-
per the water in order to reduce scald hazard potential
(see Figures 28 & 29).

– 31 –