beautypg.com

Water supply – John Wood Superflue Power Vent (75 Gallon) User Manual

Page 16

background image

7. Complete the venting installation by sealing around the

termination assembly where it passes through the out-
side wall, inside and out, with silicone or other suitable
sealant.

Water Supply

Piping Installation

Piping, fittings, and valves should be installed according to
the installation drawing (Figure 15). A pressure-reducing
valve and/or an expansion tank may be required for installa-
tions where the water pressure is high. The pressure-reduc-
ing valve should be located on the supply to the entire build-
ing in order to maintain equal hot and cold water pressure.
Important:

• Do not apply heat to the water fittings on the heater as

they may contain nonmetallic parts. If solder connec-
tions are used, solder the pipe to an adapter before
attaching the adapter to the hot and cold water fittings.

• Some models may contain energy saving heat traps to

prevent the circulation of hot water within the pipes. Do
not remove the inserts within the heat traps.

• Always use a proper grade of joint compound and be

certain that all fittings are drawn up tight.

1. Install the water piping and fittings as shown in Figure

15. Connect the cold water supply to the fitting (3/4"
NPT) marked "COLD" (or "C"). Connect the hot water
supply to the fitting (3/4" NPT) marked "HOT" (or "H").

2. The installation of unions in both the hot and cold water

supply lines is recommended.

3. The manufacturer of this water heater recommends

installing a tempering valve in the domestic hot-water
line as shown in Figure 16. These valves reduce the
point-of-use water temperature by mixing cold and hot
water. Contact a licensed plumber or the local plumbing
authority.

4. If installing the water heater in a closed water system,

install an expansion tank in the cold water line as spec-
ified under "Closed System/Thermal Expansion".

5. Install a shut-off valve in the cold-water inlet line. It

should be located close to the water heater and be eas-
ily accessible. The owner/operator must be shown the
location of this valve and be given instructions on how
to use it to shut off the water to the heater.

Filling the Water Heater

Do not insert the power cord into the electrical receptacle
until all the following steps have been completed.
1. Make sure the drain valve is closed.
2. Open all hot-water faucets served by the system to

allow air to escape from the tank.

3. Open the cold-water inlet valve.
Note: When filling, avoid water leakage. Do not allow the
insulation of the water heater to get wet as water can reduce
the effectiveness of the insulation.
4. When an uninterrupted stream of water, without appar-

ent air bubbles, flows from the open hot-water faucets,
the tank is full.

5. Close the hot-water faucets and check the system for

leaks. Repair as required and retest.

Please note the following:
DO NOT install this water heater with iron piping. The sys-
tem should be installed only with piping that is suitable for
potable (drinkable) water such as copper, CPVC, PEX or
polybutylene. DO NOT use PVC water piping.
DO NOT use any pumps, valves, or fittings that are not com-
patible with potable water.
DO NOT use valves that may cause excessive restriction to
water flow. Use full flow ball or gate valves only.

– 16 –

COLD WATER
INLET

COLD WATER

INLET VALVE

PRESSURE

REDUCING

VALVE

WITH

BYPASS

TEMPERATURE AND
PRESSURE RELIEF VALVE

HOT
WAT E R
OUTLET

UNION

DRAIN PAN CONNECT TO
PROPERLY OPERATING
FLOOR DRAIN.

DISCHARGE LINE 300mm
(12 in.) max (CANADA) OR
150mm (6 in.) max (U.S.)
ABOVE DRAIN

IN A CLOSED SYSTEM USE EITHER: 1.THERMAL EXPANSION TANK

OR

2.PRESSURE RELIEF VALVE.

Figure 15 Water Piping Installation

MASSACHUSETTS: INSTALL A
VACUUM RELIEF IN COLD WATER
LINE PER SECTION 19MGL 142

NOTE: BLOWER
ASSEMBLY NOT
SHOWN FOR
CLARITY.

Figure 14 Blower, Fittings and Vent Pipe Options

BLOWER ASS’Y WITH RUB-
BER COUPLING FOR 76mm
(3 in.) NOMINAL PVC VENT
PIPE.

CPVC VENTING DOES NOT
REQUIRE ADAPTER.

150mm (6 in.)

MIN

VENT PIPE

76mm (3 in.)

ADAPTER

RUBBER

COUPLING

CAUTION:

• Do Not Overtighten The Top And Bottom

Gear Clamps Of The Rubber Coupling.

• Do Not Apply Solvent Cement Or Silicone

To The Rubber Coupling Connection.