beautypg.com

Bell & Gossett P86271B Variable Speed NRF-VS Control with setpoint or external signal follower User Manual

Page 6

background image

6

Setpoint (Dip Switch 1=On)

The Dial on the NRF-VS allows for set point temperature
adjustment. Use a small screwdriver to turn the dial so that
the arrow lines up with the desired setpoint temperature.

• The pump speed will vary based on the difference between

the secondary loop sensor reading and the set point on the
NRF-VS.

External Signal (Dip Switch 1=Off)

Below 4mA or 2V, the pump will fully stop. At 20mA or 10V
the pump will run at full speed.

• The temperature dial is deactivated when control is in the

external signal mode.

Dip Switch 2 (Control Mode Heating or

Cooling) Available with Setpoint Only

2=Off (Heating), 2=On (Cooling)

Default 2=Off

When Heating is selected, the control will increase pump
speed when the loop temperature drops further from the
Setpoint. When loop temperature is higher than the
setpoint, the control will turn off the pump. Refer to the
outer range of 70º-200ºF shown in the scale.

• In Cooling, the control will increase pump speed the higher

the loop temperature increases above the Setpoint. When
the setpoint is reached and maintained, the control will turn
off the pump. Refer to the inner range of 30º-100ºF shown
in the scale.

Dip Switch 3 (Output Mode Linear or Logarithmic)

3=Off (Linear), 3=On (Logarithmic)

Default 3=Off

Linear

(Dip Switch 3=Off)

Linear operation is based on a linear relationship between

percent of flow of the pump and BTU output of the terminal
unit. Typical application is when the pump injects into a
constant circulating loop, which includes the terminal unit.

Logarithmic (Dip Switch 3=On)

Logarithmic operation is based on non-linear relationship

between percent of flow of the pump and BTU output of the
terminal unit. In order to achieve the desired linear output, the
NRF-VS provides a logarithmic output to compensate for the
non-linear terminal output. Typical application is when the
pump injects directly into the terminal unit.

Dip Switch 4 (Gain) Available with Setpoint Only

4=Off (Normal), 4=On (Fast)

Default 4=Off

The Gain is how aggressive the control should behave
when loop temperature is far from Setpoint. It governs the
amount of change the control applies to pump speed.

• Normal gain is typically used in applications where the

sensor temperature changes gradually during operation.

• Fast gain is typically used in applications where the sensor

temperature changes rapidly during operation.

Dip Switch 5 (Pump Exercise)

5=On (Exercise), 5=Off (No Exercise)

Default 5=On

This Dip Switch regulates if the pump should be exercised
when stayed idle for a long period of time. When set to
Exercise, pump will run at full speed for a period of 10
seconds when left in idle status for a period of 72 hours.

Heating/Cooling Mode Setting
Dip Switch 2 (Setpoint only)

Heating

Cooling

Linear

Logarithmic

Output Mode Setting
DIP Switch 3

3

3

Normal

Fast

Gain Setting
DIP Switch 4

4

4

100%

0%

100%

% of Flow

Linear

BTU Output

100%

0%

100%

% of Flow

Logarithmic

BTU Output

Logarithmic

Desired
Output

Terminal Unit Output

No Exercise

Exercise

10 Sec every
3 idle days

Pump Exercise Setting
DIP Switch 5

Temperature Dial