6

Digital inputs

6.1

Digital input #

Use the arrow keys or enter 1 to 4 to select the in-
put to be programmed.

6.2

Alarm / in use

See section 13.1 for a description between "Limit
alarm" and "In use".
Use the arrow keys to select and confirm with
ENTER.

6.3

Signal delayed

Set the delay time the input can be ON without an
alarm is being activated.
The format for the delay period is MM:SS.
Use the arrow keys (double arrow for minutes and
single arrow for seconds) or the numeric keys and
confirm with ENTER.

6.4

NO / NC

Select the input as normally open (NO) or normally
closed (NC). At NO the input is ON when the
power is connected; at NC the input is ON when
the power is disconnnected.
Use the arrow keys to select and confirm with
ENTER.

6.5

Alarm - call by telephone

Select if a digital input is to set off a telephone call
when going ON.
Use the arrow keys to select and confirm with
ENTER.

7

Digital outputs

7.1

Digital output #

Use the arrow keys or enter 1 to 4 to select the
output to be programmed.

7.2

NO / NC

Select the relay function to normally open (NO) or
normally closed (NC). At NO the relay switch will
go ON when the output is activated; at NC the
relay switch will go OFF when activated.
Use the arrow keys to select and confirm with ENTER.
At power failure all the outputs will go OFF.

7.3

Time / Fixed

A time controlled output is only ON for a certain
period of time (the ON-time) whereafter it goes
OFF. A fixed output which is turned ON must
receive a command in order to set the output OFF.
Use the arrow keys to select and confirm with
ENTER.

7.4

Time before start

Enter the delay time before start - which is the time
passing from an ON-command is transmitted until
the output responds.
The format for the delay period is MM:SS.
Use the arrow keys (double arrow for minutes and
single arrow for seconds) or the numeric keys and
confirm with ENTER.

7.5

Set ON-time

Enter the ON-time for the output. The On-time is
the period of time the output is turned ON if the
output is set to "time controlled".
The format for the delay period is MM:SS.
Use the arrow keys (double arrow for minutes and
single arrow for seconds) or the numeric keys and
confirm with ENTER.

7.6

Special functions for the digital outputs

(This menu is only accessible if 'Fixed' is selected
as described in section 7.3.)
It is possible to perform AND logic sequences by
means of the digital in- and outputs.
For example the Comtroller 702 can be program-
med to activate a digital output when 2 digital
inputs are ON. The digital signals can also derive
from exeeding a limit value on an analog input - or
a combination of a signal caused by exceeding a
limit value and an active digital input.
The following signals can be combined:
-

digital input 1 - 4

-

analog limit HIGH 1 - 2

-

analog limit LOW 1 - 2

-

combi alarm 1 - 8