ComTroller 702

5

Analog inputs

5.1

Analog input #

Select the input to be set by pressing 1. Confirm
with ENTER.

5.2

Input no 1 0 - 20 / 4 / 20 mA

Select if the signal range for the analog input
should be either 0 - 20 mA or 4 - 20 mA.
Use the arrow keys to select and confirm with
ENTER.

5.3

Input no 1 scaled 0 / 4 mA

Set the equivalent of the low mA value. If i.e. "200"
is entered, the display will read out "200" at an in-
put value of 0 / 4 mA. Use the arrow keys or the
numeric keys and confirm with ENTER.

5.4

Input no 1 scaled 20 mA

Set the equivalent of the high mA value. If i.e.
"300" is entered, the display will read out "300" at
an input value of 20 mA. Use the arrow keys or the
numeric keys and confirm with ENTER.

5.5

High limit yes / no

Select if exceeding the high limit setting on the
analog input should be registered.
Use the arrow keys to select and confirm with
ENTER.

5.6

Set high limit

Set the high limit that the analog input should
exceed before the event is registered.
Use the arrow keys to select and confirm with
ENTER.

5.7

High limit alarm / in use

See section 13.1 for a description between "Limit
alarm and In use".
Use the arrow keys to select and confirm with
ENTER.

5.8

High limit - signal delayed

Set the delay time that the input can exceed the
high limit setting without an alarm is being
activated. The format for the delay period is
MM:SS.
Use the arrow keys (double arrow for minutes and
single arrow for seconds) or the numeric keys and
confirm with ENTER.

5.9

High alarm - call by telephone

Select whether an activated high limit alarm is to
set off a telephone call.
Use the arrow keys to select and confirm with
ENTER.

5.10 Low limit yes / no
Select if exceeding the low limit setting on the ana-
log input should be registered.
Use the arrow keys to select and confirm with
ENTER.

5.11 Set low limit
Set the low limit that the analog input should
exceed before the event is registered.
Use the arrow keys to select and confirm with
ENTER.

5.12 Low limit alarm / in use
See section 13.1 for a description between "Limit
alarm" and "In use".
Use the arrow keys to select and confirm with
ENTER.

5.13 Low limit - signal delayed
Set the delay time that the input can exceed the
high limit setting without an alarm is being
activated. The format for the delay period is
MM:SS.
In the case of a power failure the analog input will
detect 0 mA. If analog low limit is set to ALARM
simultaneously with a alarm call at power failure
(see section 4.9), the delay time of the low limit
must be set to more than 30 sec.
Use the arrow keys (double arrow for minutes and
single arrow for seconds) or the numeric keys and
confirm with ENTER.

5.14 Low limit - call by telephone
Select whether an activated low limit alarm is to
set off a telephone call.
Use the arrow keys to select and confirm with
ENTER.