Fault finding – MJK Automation Shuttle Ultrasonic Level Transmitter and Sensor User Manual
Page 34

34
GB Shuttle Manual 100316
SW 838023
Fault finding
Shuttle
®
indicates
system error
constantly
Shuttle
®
Setting
Is the setting of the active measuring range (Shift + B)
correct? The active measuring range must not be set
lower than the max. possible level.
Level read-
out is not
changing
Ultrasonic
sensor
Sensor
Is the sensor mounted ABSOLUTELY VERTICAL?
mounting
It is extremely important that the sensor is firmly
mounted in a vertical position. See the section
'Mechanical mounting of sensor'.
Installation
Are there for example bit, fatty accumulations or other
site
objects disturbing the ultrasonic signal?
Setting
Has the learning function been activated? If the
learning function has not been activated, Shuttle
®
may
lock on a false echo.
Level read-
out is wrong
Ultrasonic
sensor
Sensor
Is the sensor mounted ABSOLUTELY VERTICAL?
mounting
It is extremely important that the sensor is firmly
mounted in a vertical position. See the section
'Mechanical mounting of sensor'.
Cable
Is the sensor cable extended with a not-approved
cable type and/or extended beyond 100 m?
Installation
Does the ultrasonic sensor have the same temperature
as the ambient air? Deviations will produce measuring
errors!
Shuttle
®
Setting
Shuttle
®
level readout may need adjustment.
Level
read-out is
unstable
Ultrasonic
sensor
Sensor
Is the sensor mounted ABSOLUTELY VERTICAL?
mounting
It is extremely important that the sensor is firmly
mounted in a vertical position. See the section
'Mechanical mounting of sensor'.
Is the sensor mounted firmly? The sensor should be
mounted on a suitable bracket.
Installation
Turbulence on the surface.
site
Objects on the surface that disturb the measurement.
Strong winds can bend off the echo, so it misses the
ultrasonic sensor.
Shuttle
®
Setting
Response time (Shift + C) is set too low.