“PROGRAM” mode. If it is not, press the MODE (“M”) button to change
modes.

c) To store telephone numbers in memory locations 1 through 4 (see page 8 for

pagers)

1. At the “PROGRAM: NUMBERS” prompt, press “1” (YES).

2. Press all the digits of the first number to be dialed. Check the LCD while

programming to make sure the correct numbers are pressed.

3. After inputting the entire phone number (1 + area code if needed), press

the PROGRAM/PAUSE (“P”) button (momentarily), then the “1” key.
This will store the number in location 1.

4. Repeat step 1, then press all the digits for the second number to be dialed.

Check the LCD, press the PROGRAM/PAUSE (“P”) button
(momentarily), then the “2” key. This will store the number in location 2.

5. Repeat the process, if needed, for locations 3 and 4.

NOTE: A pause may only be used when dialing a pager. When a pause is
in the dialing sequence, the unit will not deliver the voice message.