6. If you wish to change the OGM, repeat the preceding steps. The new
OGM will automatically replace the previous message.
VIII) Testing Your System
a) To verify telephone numbers and OGM without phone line connection
Follow these directions to ensure the correct telephone numbers have been
properly stored and the recorded message satisfactory.
1. Press the “M” key until “TEST: T-LINE” appears.
2. Press “1” (YES). The LCD will display the T-LINE configuration.
3. Press “1” (YES) at the “TEST: CHANNEL” prompt. The LCD will
display the Delay configuration, then the number stored in Location 1
followed by either the OGM or pager code.
4. This process will be repeated for each stored Location. Any empty
Location will be skipped. 5. Press the “M” key three times to return to the
program mode.
b) To verify telephone numbers and OGM with phone line connection
NOTE: A complete test should be performed in the “OPERATE” mode to
ensure proper operation.
1. Before conducting an actual test under “OPERATE” mode, contact each
of the designated emergency numbers (Locations 1 through 4) to advise
people that you are conducting a test. After the test, verify that they
received the message.
2. Apply power to the unit.
3. Press the “M” key until “OFF” appears in the LCD.
4. Connect the AD200-1 to an active phone line.
5. Make sure the sensor is in a non-alarm condition.
6. Press “M” until “OPERATE” appears in the LCD.
7. Trigger the sensor to simulate an alarm condition. If there are any delays
programmed, the AD200-1 will wait until they elapse before activating
and dialing.