MAINTENANCE

SCHEDULE:
• Replace thermostatic module every 4 years.

G

5. Using a spanner wrench (G)

tighten the module to approximately

12 lbf•ft (16 N•m)

Note: spanner wrenches are available

from Hoffman Specialty.

Specify part no. 600209.

A

B

6a. Reinstall and tighten the trap cover (A)

on the body (B).

b. Slowly open the steam supply valve.

c. Check for leaks and tighten connections,

if necessary.

E

F

4. Screw the new thermostatic

module (E) into the threaded port (F)

inside the trap body.