beautypg.com

Maintenance – Bell & Gossett HS 217D Dura-Stat Thermostatic Module User Manual

Page 4

background image

Xylem Inc.

8200 N. Austin Avenue

Morton Grove, Illinois 60053

Phone: (847) 966-3700

Fax: (847) 965-8379

www.xyleminc.com/brands/bellgossett

Bell & Gossett is a trademark of Xylem Inc. or one of its subsidiaries.
© 2012 Xylem Inc. HS-217d October 2012 Part No. 510669

MAINTENANCE

SCHEDULE:

• Replace Dura-Stat thermostatic module every 4 years.

H

J

6. Screw the new Dura-Stat

®

thermostatic

module (H) into the threaded port (J)
inside the trap body.

K

7. Using a 3/4” (19mm) socket wrench (K)

tighten the Dura-Stat module to
approximately 12 lbf•ft (16 N•m).

L

B

8. Place the new copper spacer (L) on the

trap body (B).

A

B

9a. Reinstall and tighten the trap cover (A)

on the body (B).

b. Slowly open the steam supply valve.