For Spirax-Sarco Trap Model TB-25; 1/2” (15mm) NPT
and Model TS-25; 1/2” (15mm) NPT

3

A

B

A

C

D

B

1. Remove the trap cover (A) from the body (B).

2a. Unscrew the coil spring (C) from

the trap cover (A).

b. Discard the coil spring (C).

3a. Remove the thermostatic element (D) from

the trap body (B).

b. Discard the old thermostatic element (D).

E

F

B

4a. Using a 5/8” (16mm) socket wrench,

remove the seat (E) and gasket (F) from
the trap body (B).

b. Discard the old seat (E) and gasket (F).

B

G

5. Using a scraper, remove any scale or

debris inside the trap body (B) especially
around the seat area (G). Do not scratch
gasket surface area.