beautypg.com

Bell & Gossett DN0153D HS Vacuum Heating Units Series HV User Manual

Warning, Hoffman specialty, Vacuum heating units series hv

background image

INSTRUCTION MANUAL

DN0153

REVISION D

Hoffman Specialty

®

Vacuum Heating Units

Series HV

(1,000-20,000 Sq. Ft. EDR)

SERIES HV

UNITS

25,000-60,000 SQ. FT/. EDR

Morton Grove, Illinois 60053

TM

SERIES HV

MODEL

SERIAL

GPM

PSI

PUMP

CFM

IN HG.

PUMP

DWGS

POWER V.

PH.

HZ 60

CONTROL V.

PH. 1

HZ 60

TOTAL

LARGEST MOTOR

F.L. AMP

F.L. AMP

DN0016

HOFFMAN SPECIALTY

®

INST

ALLER:

PLEASE LEA

VE THIS MANUAL FOR THE OWNER’S USE.

SAFETY

INSTRUCTIONS

This safety alert symbol will be used in this manual and on

the unit safety instruction decals to draw attention to safety
related instructions. When used, the safety alert symbol
means ATTENTION! BECOME ALERT! YOUR SAFETY IS
INVOLVED! FAILURE TO FOLLOW THESE INSTRUCTIONS
MAY RESULT IN A SAFETY HAZARD.

CAUTION

DO NOT RUN PUMP DRY,

SEAL DAMAGE MAY OCCUR.

INSPECT PUMP SEAL

REGULARLY FOR LEAKS,

REPLACE AS REQUIRED.

FOR LUBRICATION

REQUIREMENTS, CONSULT

SERVICE INSTRUCTIONS.

FAILURE TO FOLLOW

INSTRUCTIONS COULD

RESULT IN INJURY OR

PROPERTY DAMAGE.

P70644

EXPLOSIBLE

WARNING

DO NOT PRESSURIZE TANK.
ISOLATE TANK DURING LEAK TEST.
DO NOT RESTRICT VENT.
DO NOT PLUG OVERFLOW.
OPEN INLET VALVES SLOWLY.
DO NOT USE AS A FLASH TANK.

FAILURE TO FOLLOW
INSTRUCTIONS COULD RESULT
IN SERIOUS INJURY OR DEATH.

(2) All Units

DN0483 (Small) - DN0484 (Large)

DN0116 Units with Panel

P70644 All Units

EXPLOSIBLE

WARNING

ISOLATE TANK

DURING LEAK TEST

(2) All Units

DN0485 (Small)

DN0486 (Large)

If the decals as noted below are missing or are illegible con

-

tact your local B&G representative for a replacement.
1. Electrical connections to be made by qualified Electrician in

accordance with all National, State and Local codes.

2. Motor must have properly sized starter with properly sized

heaters to provide overload and undervoltage protection.

3. If pump, motor or piping are operating at extremely high or

low temperatures, guarding or insulation is required.

4. Operating personnel should be trained in the operation of

pumps and associated systems (condensate, boiler feed, etc.).

2

DESCRIPTION AND INST

ALLATION

The Series HV vacuum heating units are designed to serve the

dual purpose of pumping accumulated condensate back to
the boiler feed tank and maintaining vacuum in the conden-
sate system. This vacuum will draw air out of the system
on start-up and facilitate the flow of steam thru the heating
system.

One pump/vacuum producer/discharge valve assembly con-
trols both the condensate discharge and the production of
vacuum. Two pump (duplex) units have a second assembly for
backup and to provide extra capacity to handle peak loads.

Various electrical controls are offered to meet system require-
ments. These controls are normally supplied as part of the
assembled unit and a wiring diagram is furnished with the unit.
Refer to this electrical diagram as required.

The units respond to both changing condensate levels and
system vacuum requirements. The Series HV units feature a
low inlet height and therefore have a second float (in the lower
compartment). As condensate accumulates in the lower com-
partment, this float starts the pump and siphons the conden-
sate to the upper chamber.

In operation the centrifugal pump circulates condensate from
the upper compartment thru the multi-jet nozzle creating mul-
tiple jets of water entering the venturi. These jets entrain air
and gasses creating a smooth steady vacuum in the lift mani-
fold and in the condensate system. The air and gasses are
separated in the upper compartment and vented to atmos-
phere. See Figure 1.

Low system vacuum or high water in the upper compartment
or high water in the lower compartment will start the pump to
create vacuum and transfer water to the upper tank. High
water level in the upper compartment will also cause the dis-
charge valve to open.

When the vacuum and float switches have been satisfied and
the pump stops, the check valve in the lift manifold closes,
preventing the return of air and water to the system.

The solenoid operated discharge valve is opened in response
to the condensate level float switch in the upper compartment.
Controlled opening of the discharge valve holds sufficient
back pressure in the nozzle body that the vacuum producer
continues to function even when discharging condensate
(simultaneous rating).

NOZZLE BODY

MULTI-JET NOZZLE

VENTURI

PUMP SUCTION

SOLENOID OPERATED
DISCHARGE VALVE

DISCHARGE

LIFT MANIFOLD

CHECK VALVE

CENTRIFUGAL PUMP

LOWER COMPARTMENT FLOAT SWITCH

UPPER COMPARTMENT FLOAT SWITCH

STRAINER

LOW INLET

VACUUM GAUGE

VACUUM BREAKER

VACUUM SWITCH

AIR VENT

FIG. 1 CUT-AWAY VIEW OF SINGLE SERIES HV SINGLE UNIT: TYPICAL OF ALL SINGLE AND DUPLEX MODELS

AIR VENT

RECEIVER

INLET

MULTI-JET NOZZLES

VENTURI

NOZZLE

BODY

CENTRIFUGAL PUMP

DSK-1328

SOLENOID

DISCHARGE

VALVE

FIG. 2

SERIES HV VACUUM PRODUCER

SERIES HV

UNITS

1,000 – 20,000 SQ. FT/. EDR