9

V

ACUUM PUMP RUNS CONTINUOUSLY OR FAILS TO

PRODUCE SUFFICIENT VACUUM*

1.

Selector switch is set on “continuous” or “hand”.

2. The temperature of the condensate is too high. Normal

operating condensate temperature should not exceed
160°F for rated capacities. Correct the cause for high
temperature condensate.

3. There are excessive leaks in the system piping preventing

the pump from producing sufficient vacuum to satisfy the
vacuum switch setting. To confirm this, make sure pump is
primed, close inlet valve, close equalizing line valve, plug
other check valve on this line, replace vacuum breaker with
plug and observe shut-off vacuum while pump is running.

4. The vacuum or float switch electrical contacts remain in

closed position. Adjust controls.

5. The nozzle, strainer, or impeller passageways are clogged

with foreign matter. Refer to instructions for cleaning.

6. A vacuum breaker is set too low. It should not admit air at a

vacuum within the range of the vacuum switch setting.

7. The pump has lost its hurling water. There should never be

less water than shown on float adjustment sketch. Loss of
hurling water may be caused by:
(1) Discharge valve leaks due to dirt or worn seat.
(2) Orifice in guide screw in discharge valve is closed.
(3) Discharge valve bellows is ruptured.
(4) Solenoid pilot valve remains in open position.
(5) Float switch failure.
Replace the bellows discharge valve with the slenoid oper-
ated discharge valve. If the valve has already been replaced
with the solenoid operated discharge valve the loss of hurl-
ing water may be caused by:
(1) Solenoid discharge valve leaks due to dirt or worn seat.
(2) Solenoid discharge valve stuck in open position.
(3) Check valve in nozzle body is leaking.
(4) Float switch failure.

8. Check valve in equalizer line or air vent line from receiver or

accumulator tank leaks, or is installed backwards.

9. One nozzle body check valve on duplex pump remains

open, permitting air to re-circulate.

10. Pump is too small for the system.
11. Air vent line has been incorrectly piped to air vent check

valve mounted on receiver. Locate air vent check valve in
highest horizontal run.

PUMP ST

ARTS AND STOPS IN RAPID SUCCESSION

1.

A check valve in return line. Remove.

2. A partially closed inlet valve. Valve should be a gate valve

rather than globe.

3. A lift in return line at or near the pump. Low return lines will

fill with condensate between pump operations. The inertia
of the collected water may be quite great, and before the
vacuum suddenly produced by starting of the pump can set
the water in motion, the vacuum at the pump may reach the
cut-off point of the vacuum switch, thus stopping the
pump. The vacuum quickly recedes as the condensate
moves into the receiver and the pump “trips in” on vacuum
control again, thus repeating this “hunting action”.
There are two ways to correct this difficulty:
(1) If the vacuum sensing line can be relocated away from

the vacuum switch(es), connect this sensing line into the
nearest “dry” point in the return main so that the opera-
tion of the unit may be governed by the vacuum in the
system.

(2) If the nearest “dry” point on the return main is more than

2 ft. above the vacuum switch, relocate and reconnect
the switches to sense the vacuum at this point. If a
separate selector switch for “FL-Vac,” “Float,” “Hand”
operation is not already furnished with the unit, one
must be provided for each vacuum switch for installation
in control panel.

4. Elbow in return line too close to unit inlet. Correct as

described in item 3 above, or if there is no lift in the return
line at or near the pump, extend the

3

/

4

" equalizing line to

top of “dry” point on return main.

5. Equalizer line is improperly connected.
6. Leaky air vent check valve. Repair or replace.
7. Strainer clogged with dirt. Clean strainer.

PUMP MAKES NOISE

1.

The pump is working against a lower pressure than
designed for. While pump is discharging, adjust square
headed steam cock in discharge line until pressure at pump
approaches pump rated pressure. Secure adjustment of
steam cock by tightening lock nut.

2. Excessive condensate temperature. Correct system

conditions.

3. Magnetic hum or bearing noise in motor. Consult motor

manufacturer’s authorized service station nearest pump
location.

4. Starter chatters. Trouble is caused by low line voltage, poor

connections, defective starter coil, or burned contacts.

5. Pump is running backward.
6. Water hammer when discharge valve closes:

(1) Adjust steam cock to reduce discharge velocity or
(2) Install surge chamber on boiler side of discharge check

valve or

(3) Install additional check valve near boiler or
(4) Install discharge piping 1 or 2 sizes larger.

THE SYSTEM IS NOISY

1.

Banging in the steam mains is usually caused by
“imploding” in condensate lying in low points in lines. These
pockets can be eliminated by “dripping” low points,
properly supporting the pipe, or by increasing the pitch of
the lines.

2. Improper dripping of the steam mains and risers. Where

there is a rise in the steam main, or where it branches off
into a riser, a drip trap must be installed to the drain line.

3. The piping is too small to drain properly.
4. A defective trap is holding condensate in radiation.
5. A priming boiler is permitting a carry-over of water with the

steam. A priming boiler is caused by:

(1) Oil or other foreign matter. Clean boiler thoroughly.
(2) A reduction of the steam liberating area due to too high

water level in the boiler. Reduce water line.

(3) Overloading. Reduce firing rate.
(4) Undersized steam outlet area, resulting in velocities in

excess of 15 to 25 ft. per second.

*Product life and product efficiency are greatly affected by system maintenance. A
tight (leak-free) system with properly functioning traps is essential for efficient
operation.