CDT900 Series Touchscreen Programmable Thermostata
Table 9. Sequence of Operation for Conventional Systems.
System Setting
Fan Setting
Call for Action
Energize Terminals
Screen Message
Off Auto
None
None
None
Cool Auto None None None
Cool or Auto
Auto
Stage 1 Cooling
Y, G
Cool On
Cool or Auto
Auto
Stage 1 and Stage 2
Cooling
Y, Y2b, G
Cool On
Heat Auto
None None None
Heat or Auto
Auto
Stage 1 Heating
W, Ga
Heat On
Heat or Auto
Auto
Stage 1 and Stage 2
Heating
W, W2c, Ga
Heat On
a
G energizes only if Installer Setup number 0180 is set to Electric.
b
If Installer Setup System type is set to two stages of cooling.
c
If Installer Setup System type is set to two stages of heating.