Comfort Stat CDT901 User Manual
Page 54

CDT900 Series Touchscreen Programmable Thermostata
Table 3.installer Setup Menu. (CONTINUES)
Installer Setup
Number
Installer Setup
Name
Settings Notes
0270
Cycles per hour (cph)
for Emer
3-3 cph for hot water systems and high
efficiency (90% or better) furnaces
5-5 cph for standard fossil fuel forced air
(less than 90% efficient or better) systems
9-9 cph for electric strip heat for heat pumps
Only shown if 2H/1C or 3H/2C
heat pump is selected.
0280 Continuous
Backlight
0-Backlight function disable
1-Backlight function enable
.
0300 Changeover
0-manual changeover (factory setting)
1-auto changeover
0310 Deadband
Heating and cooling setpoints can be set no
closer than chosen value:
2-2°F (1.5°C)
3-3°F (2°C)
4-4°F (2.5°C)
5-5°F (3°C)
6-6°F (3.5°C)
7-7°F (4°C)
8-8°F (4.5°C)
9-9°F (5°C)
Shown only if automatic
changeover is selected.
0320
Temperature Indication
Scale
0-fahrenheit temperature display (factory
setting)
1-celsius temperature display
when it is changed, the sched
need to be reprogrammed)