Cdt900 series touchscreen programmable thermostata, Table 3.installer setup menu. (continues) 58 – Comfort Stat CDT901 User Manual
Page 59

CDT900 Series Touchscreen Programmable Thermostata
Installer Setup
Number
Installer Setup
Name
Settings Notes
0690
Temperature Control in
Cool
1-less aggressive temperature control (could
cause temperature undershoot)
2-Standard temperature control in cooling
(factory setting)
3-more aggressive temperature control
(could cause temperature overshoot)
Applies to recovery ramp.
Choose 1 if getting
temperature overshoot.
Choose 3 if getting
temperature undershoot.
0700
Temperature Display
Offset
-3°F (-1.5°C)
-2°F (-1°C)
-1°F (-.5°C)
0°F (0. °C) (no difference in displayed
temperature and actual room temperature )
1°F (.5°C)
2°F (1°C
3°F (1.5°C)
0710 Reset
Thermostat
0-no thermostat reset.
1-resets all Installer Setup Options to default
values and resets schedule to default setting.
Only calendar settings and
time are retained.
Table 3.installer Setup Menu. (CONTINUES)
58