7.5.4 Control methods
Table 7. Three different control methods:
1
EP
Electronic potentiometer function.
Stepless control using a 2-step controller.
2
MS
Multistep control (2 steps)
Requires programmable digital inputs for speed reference steps
3
AU
Automation control for any control device with an output in the range of 0 –
10V
E.g. radio controls, process computers.
All control methods are available without any changes in the hardware or software.
The control mode is selected by parameter P1.1.11 Input set. The parameter assigns digital inputs S1, S2
and DID3-DID5. It is not possible to change the functions of the inputs separately. The state of inputs can be
checked from parameter V2.3.
Table 8. Control Modes
Control Mode
MS2
(stop-lim)
EP2
(stop-lim)
AU (Ain1)
Must not
be used
Parameter P1.1.11
0
2
7
1,3,4,5,6
Signal
Terminal
S1
DID1
S1
S1
S1
-
S2
DID2
S2
S2
S2
-
DID3
DID3
MAX
AP
S11/S21
-
DID4
DID4
S12
S12
S12
-
DID5
DID5
S22
S22
S22
-
S1
Drive command direction S1
S2
Drive command direction S2
AP
Acceleration command
MAX
Maximum frequency
S12
Stop-limit forward
S22
Stop-limit reverse
S11/S21
Common slowdown limit
Table 9. Desired speed levels for multi-step control mode are selected with following parameters
Speed
Parameter
Input
Minimum
P1.1.4
S1/S2
Maximum
P1.1.5
MAX