Fuel installation, Chapter 5 fuel installation, Fuel supply liquid lpg vapor lpg natural gas – Grain Systems PNEG-1820 User Manual
Page 13: Fuel supply, Liquid lpg, Vapor lpg, Natural gas

PNEG-1820 CE Compliant Top Dry Series 2000 Autoflow
13
5. Fuel Installation
Fuel Supply
The dryer requires a suitable fuel supply. Refer to fuel specifications
for fuel
flow requirements.
Liquid LPG
Dryers with internal vaporizers require LPG in liquid form.
Vapor LPG
Dryers without internal vaporizers require LPG in vapor form.
LPG tanks must have adequate vaporizing capacity to supply the maximum fuel flow given in
fuel specifications
. Alternatively and external vaporizer may be used.
For twin fan units, double the fuel flow.
Primary pressure regulation is required at the tank, including over pressure protection.
Supply pressure at the dryer should be 1.5 bar-2.0 bar (150 kPa-200 kPa).
Natural Gas
Natural gas dryers require a supply capable of the maximum flow given in fuel specifications
For twin fan units, double the flow.
Minimum supply pressure at the dryer must be 750 mBar (75 kPa).
Primary pressure regulation should include over pressure protection.