beautypg.com

Milton CAT C15 500 ekW 625 kVA 60 Hz 1800 rpm 480 Volts Performance Data User Manual

Page 4

background image

EMISSIONS DATA

EPA TIER-2 2006 - ---- *************************************************** B5
Gaseous emissions data measurements are consistent with those described in
EPA 40 CFR PART 89 SUBPART D and ISO 8178 for measuring HC, CO, PM, and NOx

Gaseous emissions values are WEIGHTED CYCLE AVERAGES and are in compliance
with the following non-road regulations:

LOCALITY AGENCY/LEVEL MAX LIMITS - g/kW-hr
----------------- ------------ -----------------------------------
U.S. (incl Calif) EPA/TIER-2 CO:3.5 NOx + HC:6.4 PM:0.2

REFERENCE EXHAUST STACK DIAMETER

--

WET EXHAUST MASS

6,428.7 LB/HR

WET EXHAUST FLOW (941.00 F STACK TEMP )

3,845.77 CFM

WET EXHAUST FLOW RATE ( 32 DEG F AND 29.98 IN HG )

1,319.00 STD CFM

DRY EXHAUST FLOW RATE ( 32 DEG F AND 29.98 IN HG )

1,208.82 STD CFM

FUEL FLOW RATE

36 GAL/HR

Page 4 of 8

Performance Data

9/21/2009

file://J:\Website content\C15 models\C15 Rated 500 kW Performance Data_files\cat.edis.t...