beautypg.com

Milton CAT G130LG 130kW_163kVA Spec Sheet User Manual

Page 3

background image

STARTING CAPABILITIES (sKVA)

FUEL

Natural Gas

Propane Vapor

Single-Phase 120/240VAC @1.0pf

117

Amps: 488

130

Amps: 542

Three-Phase 120/208VAC @0.8pf

122

Amps: 423

130

Amps: 451

Three-Phase 120/240VAC @0.8pf

122

Amps: 367

130

Amps: 391

Three-Phase 277/480VAC @0.8pf

122

Amps: 183

130

Amps: 195

Three-Phase 346/600VAC @0.8pf

122

Amps: 147

130

Amps: 156

sKVA vs. Voltage Dip

480VAC

208/240VAC

Alternator

kW

10%

15%

20%

25%

30%

35%

10%

15%

20%

25%

30%

35%

Standard

130

116

174

232

290

348

406

87

131

174

218

261

305

Upsize 1

150

133

199

265

332

398

464

100

149

199

249

299

348

Upsize 2

200

187

280

373

467

560

653

140

210

280

350

420

490

COOLING

COMBUSTION AIR REQUIREMENTS

ENGINE

EXHAUST

STANDBY

Flow at Rated Power

cfm

379

STANDBY

Rated Engine Speed

rpm

3000

Horsepower at Rated kW**

hp

189

Piston Speed

ft/min

2085

BMEP

psi

132

** Refer to “Emissions Data Sheet” for maximum bHP for EPA and SCAQMD permitting purposes.

STANDBY

Exhaust Flow (Rated Output)

cfm (m

3

/min)

1206 (34.1)

Maximum Recommended Back Pressure

inHg

1.5

Exhaust Temp (Rated Output)

ºF (ºC)

1250 (676.7)

Exhaust Outlet Size (Open Set)

in

2.5"

POWER RATINGS (kW)

Fuel Consumption Rates*

Natural Gas

Propane Vapor

Percent Load

ft

3

/hr

m

3

/hr

Percent Load

ft

3

/hr

gal/hr

m

3

/hr

25%

600

17.0

25%

248

6.8

7.0

50%

1000

28.3

50%

414

11.4

11.7

75%

1325

37.5

75%

548

15.1

15.5

100%

1786

50.6

100%

739

20.4

20.9

* Refer to "Emissions Data Sheet" for maximum fuel flow for EPA and SCAQMD permitting purposes.

STANDBY

Air Flow (inlet air combustion and radiator)

ft

3

/min (m

3

/min)

5979 (169.3)

System Coolant Capacity

Gal (Liters)

6.3 (23.9)

Heat Rejection to Coolant

BTU/hr

500,080

Max. Operating Air Temp on Radiator

ºF (ºC)

122 (50)

Max. Ambient Temperature

ºF (ºC)

104 (40)

Maximum Radiator Backpressure

in H

2

O

1.50

3 of 5

G130LG

operating data (60Hz)

G130LG 130kW

*

*

*PME Only

Deration – Operational characteristics consider maximum ambient conditions. Derate factors may apply under atypical site conditions. All performance ratings in accordance with ISO3046,
BS5514, ISO8528 and DIN6271 standards.