Milton CAT G130LG 130kW_163kVA Spec Sheet User Manual
Page 3

STARTING CAPABILITIES (sKVA)
FUEL
Natural Gas
Propane Vapor
Single-Phase 120/240VAC @1.0pf
117
Amps: 488
130
Amps: 542
Three-Phase 120/208VAC @0.8pf
122
Amps: 423
130
Amps: 451
Three-Phase 120/240VAC @0.8pf
122
Amps: 367
130
Amps: 391
Three-Phase 277/480VAC @0.8pf
122
Amps: 183
130
Amps: 195
Three-Phase 346/600VAC @0.8pf
122
Amps: 147
130
Amps: 156
sKVA vs. Voltage Dip
480VAC
208/240VAC
Alternator
kW
10%
15%
20%
25%
30%
35%
10%
15%
20%
25%
30%
35%
Standard
130
116
174
232
290
348
406
87
131
174
218
261
305
Upsize 1
150
133
199
265
332
398
464
100
149
199
249
299
348
Upsize 2
200
187
280
373
467
560
653
140
210
280
350
420
490
COOLING
COMBUSTION AIR REQUIREMENTS
ENGINE
EXHAUST
STANDBY
Flow at Rated Power
cfm
379
STANDBY
Rated Engine Speed
rpm
3000
Horsepower at Rated kW**
hp
189
Piston Speed
ft/min
2085
BMEP
psi
132
** Refer to “Emissions Data Sheet” for maximum bHP for EPA and SCAQMD permitting purposes.
STANDBY
Exhaust Flow (Rated Output)
cfm (m
3
/min)
1206 (34.1)
Maximum Recommended Back Pressure
inHg
1.5
Exhaust Temp (Rated Output)
ºF (ºC)
1250 (676.7)
Exhaust Outlet Size (Open Set)
in
2.5"
POWER RATINGS (kW)
Fuel Consumption Rates*
Natural Gas
Propane Vapor
Percent Load
ft
3
/hr
m
3
/hr
Percent Load
ft
3
/hr
gal/hr
m
3
/hr
25%
600
17.0
25%
248
6.8
7.0
50%
1000
28.3
50%
414
11.4
11.7
75%
1325
37.5
75%
548
15.1
15.5
100%
1786
50.6
100%
739
20.4
20.9
* Refer to "Emissions Data Sheet" for maximum fuel flow for EPA and SCAQMD permitting purposes.
STANDBY
Air Flow (inlet air combustion and radiator)
ft
3
/min (m
3
/min)
5979 (169.3)
System Coolant Capacity
Gal (Liters)
6.3 (23.9)
Heat Rejection to Coolant
BTU/hr
500,080
Max. Operating Air Temp on Radiator
ºF (ºC)
122 (50)
Max. Ambient Temperature
ºF (ºC)
104 (40)
Maximum Radiator Backpressure
in H
2
O
1.50
3 of 5
G130LG
operating data (60Hz)
G130LG 130kW
*
*
*PME Only
Deration – Operational characteristics consider maximum ambient conditions. Derate factors may apply under atypical site conditions. All performance ratings in accordance with ISO3046,
BS5514, ISO8528 and DIN6271 standards.