POWER RATINGS (kW)
STARTING CAPABILITIES (sKVA)
FUEL
COOLING
COMBUSTION AIR REQUIREMENTS
ENGINE
EXHAUST
Natural Gas
Three-Phase 120/208VAC @0.8pf
300 kW
Amps: 1041
Three-Phase 120/240VAC @0.8pf
300 kW
Amps: 902
Three-Phase 277/480VAC @0.8pf
300 kW
Amps: 451
Three-Phase 346/600VAC @0.8pf
300 kW
Amps: 361
sKVA vs. Voltage Dip
480VAC
208/240VAC
Alternator
kW
10%
15%
20%
25%
30%
35%
10%
15%
20%
25%
30%
35%
Standard
300
303
454
605
757
908
1059
227
341
454
568
681
794
Upsize 1
–
Fuel Consumption Rates*
Natural Gas
Percent Load
ft
3
/hr
m
3
/hr
25%
1671
47.3
50%
2162
61.2
75%
3048
86.3
100%
3939
111.5
* Refer to "Emissions Data Sheet" for maximum fuel flow for EPA and SCAQMD permitting purposes.
Air Flow (inlet air combustion and radiator)
ft
3
/min (m
3
/min)
20,400 (577.7)
System Coolant Capacity
Gal (Liters)
15 (56.8)
Heat Rejection to Coolant
BTU/hr
1,024,140
Max. Operating Air Temp on Radiator
ºF (ºC)
122 (50)
Max. Ambient Temperature
ºF (ºC)
104 (40)
Maximum Radiator Backpressure
"H
2
O
1.50
Flow at Rated Power
cfm
1200
Rated Engine Speed
rpm
2300
Horsepower at Rated kW**
hp
454
Piston Speed
ft/min
2262
BMEP
psi
203.5
** Refer to “Emissions Data Sheet” for maximum bHP for EPA and SCAQMD permitting purposes.
Exhaust Flow (Rated Output)
cfm (m
3
/min) 4335 (122.8)
Max. Backpressure (Post Silencer)
inHg
1.5
Exhaust Temp (Rated Output)
ºF (ºC) 1490 (810)
Exhaust Outlet Size (Open Set)
in
5.0"
3 of 5
G300LG
operating data (60Hz)
G300LG 300kW
Deration – Operational characteristics consider maximum ambient conditions. Derate factors may apply under atypical site conditions. All performance ratings in accordance with ISO3046,
BS5514, ISO8528 and DIN6271 standards.