Milton CAT G300LG 300kW_375kVA Spec Sheet User Manual

Page 3

background image

POWER RATINGS (kW)

STARTING CAPABILITIES (sKVA)

FUEL

COOLING

COMBUSTION AIR REQUIREMENTS

ENGINE

EXHAUST

Natural Gas

Three-Phase 120/208VAC @0.8pf

300 kW

Amps: 1041

Three-Phase 120/240VAC @0.8pf

300 kW

Amps: 902

Three-Phase 277/480VAC @0.8pf

300 kW

Amps: 451

Three-Phase 346/600VAC @0.8pf

300 kW

Amps: 361

sKVA vs. Voltage Dip

480VAC

208/240VAC

Alternator

kW

10%

15%

20%

25%

30%

35%

10%

15%

20%

25%

30%

35%

Standard

300

303

454

605

757

908

1059

227

341

454

568

681

794

Upsize 1

Fuel Consumption Rates*

Natural Gas

Percent Load

ft

3

/hr

m

3

/hr

25%

1671

47.3

50%

2162

61.2

75%

3048

86.3

100%

3939

111.5

* Refer to "Emissions Data Sheet" for maximum fuel flow for EPA and SCAQMD permitting purposes.

Air Flow (inlet air combustion and radiator)

ft

3

/min (m

3

/min)

20,400 (577.7)

System Coolant Capacity

Gal (Liters)

15 (56.8)

Heat Rejection to Coolant

BTU/hr

1,024,140

Max. Operating Air Temp on Radiator

ºF (ºC)

122 (50)

Max. Ambient Temperature

ºF (ºC)

104 (40)

Maximum Radiator Backpressure

"H

2

O

1.50

Flow at Rated Power

cfm

1200

Rated Engine Speed

rpm

2300

Horsepower at Rated kW**

hp

454

Piston Speed

ft/min

2262

BMEP

psi

203.5

** Refer to “Emissions Data Sheet” for maximum bHP for EPA and SCAQMD permitting purposes.

Exhaust Flow (Rated Output)

cfm (m

3

/min) 4335 (122.8)

Max. Backpressure (Post Silencer)

inHg

1.5

Exhaust Temp (Rated Output)

ºF (ºC) 1490 (810)

Exhaust Outlet Size (Open Set)

in

5.0"

3 of 5

G300LG

operating data (60Hz)

G300LG 300kW

Deration – Operational characteristics consider maximum ambient conditions. Derate factors may apply under atypical site conditions. All performance ratings in accordance with ISO3046,
BS5514, ISO8528 and DIN6271 standards.