beautypg.com

Milton CAT G50LG 50kW_63kVA Alt Data User Manual

50kw, Alternator data, Alternator decrement curve

background image

50kW

Alternator Data

Information contained in this publication may be considered confidential.

Discretion is recommended when distributing.

Materials and specifications are subject to change without notice.

© 2010 Caterpillar
All rights reserved.

Printed in U.S.A.

kW
kVA

Telephone Influence Factor

Type Excitation

Synchronous Speed

Connections

Maximum Overspeed

Efficiency @ 1.0 Power Factor

208/240

480

Number of Bearings

20% Load

87.76 89.1

Insulation System

40% Load

88.26 89.6

Excitation System

60% Load

88.75 90.1

80% Load

88.65 90.0

100% Load

88.45 89.8

100% @ 0.8 PF

88.06 89.4

Subtransient Reactance p.u.

0.17 0.15

Transient Reactance

0.028 0.25

Synchronous Reactance

4.69 4.65

10% 15% 20% 25% 30% 35%

Negative Sequence Reactance

0.41 0.33

26

39

52

65

77

90

Zero Sequence Reactance

0.2 0.18

34

52

69

86

103

120

Short Circuit Ratio

0.38 0.38

Excitation Voltage

170 190

Excitation Current @ 50 kW

4.2 4.8

Lamination Type

390 390

Design and specifications are subject to change without notice.

Date 01/2010

Rev 1

Alternator Ratings

(Series Wye Testing)

Machine Parameters @ Max kW Ratings

120 º

80 º

105 º

Temp Rise º C

Class H

<5%

Waveform Distortion

<50

1800 rpm

480

3300 rpm

1 Sealed Ball

Class H

50

kW Rating

Termperature

Rise is based

40º C Ambient

Temperature Rise vs Output (0.8 pf)

Options - - - - - - - - - - - -

Voltage

Instantaneous Voltage Dip

208, 240

37
42

Machine Parameters Continued

50

62.5

Dir/Brusls

12 Lead

208/480v

ALTERNATOR DECREMENT CURVE

100

1000

0.01

0.1

1

10

100

Seconds

A

m

pe

re

s

Alt Damage

Internal Control shutdown

3-Ø Short Circuit Current

All data at 480 Volt Direct Exc