beautypg.com

Operating data – Milton CAT G25LTA 25 kW Spec Sheet User Manual

Page 3

background image

G25LTA

KW RATING

25

ENGINE SIZE

2.4 Liter 4 cylinder

GENERATOR OUTPUT VOLTAGE/KW - 60Hz

KW

AMP

CB Size

120/240V, 1-phase, 1.0 pf

25

104

125

120/208V, 3-phase, 0.8 pf

25

87

100

277/480V, 3-phase, 0.8 pf

25

38

40

120/240V, 3-phase, 0.8 pf

25

75

80

GENERATOR LOCKED ROTOR KVA
AVAILABLE @ VOLTAGE DIP OF 35%
Single phase or 208 3-phase

43

480V 3-phase

57

ENGINE FUEL CONSUMPTION

(Natural Gas) (Propane)

Natural Gas

Propane

(ft

3

/hr.)

(gal/hr.)

cu ft/hr

Exercise cycle

60

0.65

24

25% of rated load

140

1.53

56

50% of rated load

220

2.40

87

75% of rated load

300

3.27

119

100% of rated load

380

4.15

151


ENGINE COOLING
Air flow

(inlet air including alternator and combustion air)

ft

3

/min.

1,500

System coolant capacity

US gal.

2.5

Heat rejection to coolant

BTU/hr.

95,000

Max. operating air temp. on radiator

°C (°F)

60 (150)

Max. ambient temperature

°C (°F)

50 (140)

COMBUSTION AIR REQUIREMENTS
Flow at rated power 60 Hz

cfm

70


SOUND EMISSIONS IN DBA
Exercising at 7 meters

54

Normal operation at 7 meters

60


EXHAUST
Exhaust flow at rated output 60 Hz

cfm

220

Exhaust temp. at muffler outlet

°F

975

ENGINE PARAMETERS
Rated synchronous RPM

60 Hz

1800

HP at rated KW

60 Hz

40

POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature Deration

3% for every 10 °C above - °C

25

1.65% for every 10 °F above - °F

77

Altitude Deration

1% for every 100 m above - m

183

3% for every 1000 ft. above - ft.

600

OPERATING DATA

RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings
apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is
no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice.
KW rating is based on LPG Fuel and may derate with natural gas.

G25LTA