STARTING CAPABILITIES (sKVA)

FUEL

Natural Gas

Three-Phase 120/208VAC @0.8pf

250

Amps: 868

Three-Phase 120/240VAC @0.8pf

250

Amps: 752

Three-Phase 277/480VAC @0.8pf

250

Amps: 376

Three-Phase 346/600VAC @0.8pf

250

Amps: 301

sKVA vs. Voltage Dip

480VAC

208/240VAC

Alternator

kW

10%

15%

20%

25%

30%

35%

10%

15%

20%

25%

30%

35%

Standard

250

263

395

527

658

790

922

197

296

395

494

593

692

Upsize 1

300

303

454

605

757

908

1059

227

341

454

568

681

794

COOLING

COMBUSTION AIR REQUIREMENTS

ENGINE

EXHAUST

Flow at Rated Power

cfm

453

Rated Engine Speed

rpm

1800

Horsepower at Rated kW**

hp

400

Piston Speed

ft/min

1773

BMEP

psi

223.9

** Refer to “Emissions Data Sheet” for maximum bHP for EPA and SCAQMD permitting purposes.

Exhaust Flow (Rated Output)

cfm (m

3

/min)

1602 (45.4)

Maximum Recommended Back Pressure

inHg

1.5

Exhaust Temp (Rated Output)

ºF (ºC)

1450 (788)

Exhaust Outlet Size (Catalyst)

in

5.0"

POWER RATINGS (kW)

Fuel Consumption Rates*

Natural Gas

Percent Load

ft

3

/min

ft

3

/hr

m

3

/hr

25%

22.8

1368

38.7

50%

34.2

2052

58.1

75%

47.8

2868

81.2

100%

58.7

3522

99.7

* Refer to "Emissions Data Sheet" for maximum fuel flow for EPA and

SCAQMD permitting purposes.

Air Flow (inlet air combustion and radiator)

ft

3

/min (m

3

/min)

10,078 (285.4)

System Coolant Capacity

Gal (Liters)

19 (71.9)

Heat Rejection to Coolant

BTU/hr

788,204

Max. Operating Air Temp on Radiator

ºF (ºC)

122 (50)

Max. Ambient Temperature

ºF (ºC)

104 (40)

Maximum Radiator Backpressure

in H

2

O

0.5

3 of 5

G250LG

operating data (60Hz)

G250LG 250kW

Deration – Operational characteristics consider maximum ambient conditions. Derate factors may apply under atypical site conditions. All performance ratings in accordance with ISO3046,
BS5514, ISO8528 and DIN6271 standards.