Milton CAT G250LG4 250kW_313kVA Spec Sheet User Manual
Page 3

STARTING CAPABILITIES (sKVA)
FUEL
Natural Gas
Three-Phase 120/208VAC @0.8pf
250
Amps: 868
Three-Phase 120/240VAC @0.8pf
250
Amps: 752
Three-Phase 277/480VAC @0.8pf
250
Amps: 376
Three-Phase 346/600VAC @0.8pf
250
Amps: 301
sKVA vs. Voltage Dip
480VAC
208/240VAC
Alternator
kW
10%
15%
20%
25%
30%
35%
10%
15%
20%
25%
30%
35%
Standard
250
263
395
527
658
790
922
197
296
395
494
593
692
Upsize 1
300
303
454
605
757
908
1059
227
341
454
568
681
794
COOLING
COMBUSTION AIR REQUIREMENTS
ENGINE
EXHAUST
Flow at Rated Power
cfm
453
Rated Engine Speed
rpm
1800
Horsepower at Rated kW**
hp
400
Piston Speed
ft/min
1773
BMEP
psi
223.9
** Refer to “Emissions Data Sheet” for maximum bHP for EPA and SCAQMD permitting purposes.
Exhaust Flow (Rated Output)
cfm (m
3
/min)
1602 (45.4)
Maximum Recommended Back Pressure
inHg
1.5
Exhaust Temp (Rated Output)
ºF (ºC)
1450 (788)
Exhaust Outlet Size (Catalyst)
in
5.0"
POWER RATINGS (kW)
Fuel Consumption Rates*
Natural Gas
Percent Load
ft
3
/min
ft
3
/hr
m
3
/hr
25%
22.8
1368
38.7
50%
34.2
2052
58.1
75%
47.8
2868
81.2
100%
58.7
3522
99.7
* Refer to "Emissions Data Sheet" for maximum fuel flow for EPA and
SCAQMD permitting purposes.
Air Flow (inlet air combustion and radiator)
ft
3
/min (m
3
/min)
10,078 (285.4)
System Coolant Capacity
Gal (Liters)
19 (71.9)
Heat Rejection to Coolant
BTU/hr
788,204
Max. Operating Air Temp on Radiator
ºF (ºC)
122 (50)
Max. Ambient Temperature
ºF (ºC)
104 (40)
Maximum Radiator Backpressure
in H
2
O
0.5
3 of 5
G250LG
operating data (60Hz)
G250LG 250kW
Deration – Operational characteristics consider maximum ambient conditions. Derate factors may apply under atypical site conditions. All performance ratings in accordance with ISO3046,
BS5514, ISO8528 and DIN6271 standards.