Milton CAT G130LG 130kW_163kVA Level 1 Attenuated Enclosure Sound Data User Manual
Sound test results, Genset: enclosure
![background image](/manuals/268353/1/background.png)
Genset:
Enclosure:
Right
Left
Notes:
1. All positions 23 ft (7M) from side faces of generator set.
2. Generator operating at full load.
3. Test conducted on a 100 foot diameter asphault surface.
4. Non-enclosed sets do not include exhaust sound during testing.
Sound Test Results
G130LG 6.8L
Sound Attenuated Enclosure
Front
Back
Measured Sound Levels - 60 Hz
78.1
77.0
76.4
76.7
64
66
68
70
72
74
76
78
80
82
84
86
88
90
1
2
3
4
Position Number
dB
(A
) @ 7 Meter
s
Actual
Average
Avg. 77.1 dBA
RADIATOR END
GENERATOR END
Pos 1
Pos 2
Pos 3
Pos 4
DATA SUBJECT TO CHANGE WITHOUT NOTICE
0603010SSD 5/06