beautypg.com

Milton CAT D100-6_S 100 kW Automatic Voltage Regulator R250 User Manual

Automatic voltage regulator – r250, Exclusively from your caterpillar, Dealer

background image

G E N E R A T O R S

AUTOMATIC VOLTAGE
REGULATOR – R250

The circuitry of the R250 Automatic Voltage
Regulator (AVR) provides closed loop control
of the generator output voltage by regulating
the exciter field current. The R250 is powered
by the shunt field excitation system and is fitted
as standard on:

– 1000 Series Generators
– 2000 Series Generators
– 3000 Series Generators

SPECIFICATION:

Steady state voltage regulation ± 0.5%

Voltage supply and sensing 85 to 139 volts
(50/60 Hz)

Rapid response time (500 ms) for a transient
voltage variation amplitude of ± 20%

Capable of remote voltage adjustment ± 5%

LOAD ADJUSTMENT MODULE (LAM):
On load impact, the rotation speed of the generating
set decreases. When it passes below the preset
frequency threshold, the LAM causes the voltage
to drop by approximately 13% and consequently
the amount of active load applied is reduced by
approximately 25% until the speed reaches its
rated value again.

ADJUSTMENT CAPABILITY:

The R250 AVR features the following adjustment
capabilities: (Please note that no adjustments
should be made prior to careful consultation
of the generator installation and maintenance
manual).

Generator output voltage adjustment

Stability adjustment

Underspeed threshold adjustment

50 Hz or 60 Hz frequency option

Remote voltage adjustment option

Information contained in this publication may be considered confidential.

Discretion is recommended when distributing.

www.cat-electricpower.com

Market: N. America

Materials and specifications are subject to change without notice.

CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow” and the POWER EDGE

© 2007 Caterpillar

LEHE7341-00 (09-07)

trade dress, as well as corporate and product identity used herein, are trademarks

All Rights Reserved.

of Caterpillar and may not be used without permission.

Printed in U.S.A.

4 x holes Ø 5.8 x

50 x 115 mm

140 mm

75 mm

R 250

VO

L

T

FREQ. & L.A.

M. CONFIG.

ST

AB

F1

Slow fuse
250V 8 A

P1

Voltage

P2

Stability

110

E+ E-

0V

0

9

8

7

6

5

4

3

2

1

o

1

2

3

5

6

7

9

8

4

60Hz

65Hz

57Hz

47.5Hz

50Hz

KNEE

SPECIA L

LAM

OFF

OFF

13%

13%

25%

25%

LAM

KNEE

KNEE

LAM OFF

LAM OFF

LAM OFF

External potentiometrer
for voltage adjusting

ST4

Option

Frequency selector 50 Hz/
60 Hz for U/F function
and LAM adjustment

Exclusively from your Caterpillar

®