beautypg.com

Technical data – Milton CAT C18 550 kW 688 kVA 60 Hz 1800 rpm 480 Volts Spec Sheet User Manual

Page 4

background image

®

STANDBY 550 ekW 688 kVA

60 Hz 1800 rpm 480 Volts

TECHNICAL DATA

Open Generator Set - - 1800 rpm/60 Hz/480 Volts

DM8517

EPA Certified Tier 2

Generator Set Package Performance

Genset Power rating @ 0.8 pf
Genset Power rating with fan

687.5 kVA
550 ekW

Coolant to aftercooler

Coolant to aftercooler temp max

49 º C

120 º F

Fuel Consumption

100% load with fan
75% load with fan
50% load with fan

151.1 L/hr

39.9 Gal/hr

118.2 L/hr

31.2 Gal/hr

86.0 L/hr

22.7 Gal/hr

Cooling System

1

Air flow restriction (system)
Air flow (max @ rated speed for radiator arrangement)
Engine Coolant capacity with radiator/exp. tank
Engine coolant capacity
Radiator coolant capacity

0.12 kPa

0.48 in. water

804 m³/min

28393 cfm

81.8 L

21.6 gal

20.8 L

5.5 gal

61.0 L

16.1 gal

Inlet Air

Combustion air inlet flow rate

46.0 m³/min

1624.5 cfm

Exhaust System

Exhaust stack gas temperature
Exhaust gas flow rate
Exhaust flange size (internal diameter)
Exhaust system backpressure (maximum allowable)

520.6 º C

969.1 º F

128.9 m³/min

4552.1 cfm

203 mm

8 in

10.0 kPa

40.2 in. water

Heat Rejection

Heat rejection to coolant (total)
Heat rejection to exhaust (total)
Heat rejection to aftercooler
Heat rejection to atmosphere from engine
Heat rejection to atmosphere from generator

180 kW

10237 Btu/min

572 kW

32530 Btu/min

134 kW

7621 Btu/min

107 kW

6085 Btu/min

32.6 kW

1854.0 Btu/min

Alternator

2

Motor starting capability @ 30% voltage dip
Frame
Temperature Rise

1445 skVA
LC6114G
130 º C

234 º F

Emissions (Nominal)

3

NOx g/hp-hr
CO g/hp-hr
HC g/hp-hr
PM g/hp-hr

5.56 g/hp-hr
.35 g/hp-hr
.01 g/hp-hr
.033 g/hp-hr

1

For ambient and altitude capabilities consult your Caterpillar dealer. Air flow restriction (system) is added to existing restriction from

factory.

2

Generator temperature rise is based on a 40º C (104º F) ambient per NEMA MG1-32.

3

Emissions data measurement procedures are consistent with those described in EPA CFR 40 Part 89, Subpart D & E and ISO8178-1 for

measuring HC, CO, PM, NOx. Data shown is based on steady state operating conditions of 77ºF, 28.42 in HG and number 2 diesel fuel
with 35º API and LHV of 18,390 btu/lb. The nominal emissions data shown is subject to instrumentation, measurement, facility and engine
to engine variations. Emissions data is based on 100% load and thus cannot be used to compare to EPA regulations which use values
based on a weighted cycle.

May 06 2009 13:19 PM

4