Milton CAT 3512C 1500 kW 1875 kVA 60 Hz 1800 rpm 480 Volts Performance Data User Manual

Page 6

background image

EMISSIONS DATA

EPA TIER-2 2006 - *************************************************** B5
Gaseous emissions data measurements are consistent with those described in
EPA 40 CFR PART 89 SUBPART D and ISO 8178 for measuring HC, CO, PM, and NOx

Gaseous emissions values are WEIGHTED CYCLE AVERAGES and are in compliance
with the following non-road regulations:

LOCALITY AGENCY/LEVEL MAX LIMITS - g/kW-hr
----------------- ------------ -----------------------------------
U.S. (incl Calif) EPA/TIER-2 CO:3.5 NOx + HC:6.4 PM:0.2

REFERENCE EXHAUST STACK DIAMETER

8 IN

WET EXHAUST MASS

21,100.4 LB/HR

WET EXHAUST FLOW (762.80 F STACK TEMP )

11,071.16 CFM

WET EXHAUST FLOW RATE ( 32 DEG F AND 29.98 IN HG )

4,321.00 STD CFM

DRY EXHAUST FLOW RATE ( 32 DEG F AND 29.98 IN HG )

3,958.78 STD CFM

FUEL FLOW RATE

105 GAL/HR

Page 6 of 10

Performance Data

12/04/2009