beautypg.com

Milton CAT G275LG 275kW_344kVA Spec Sheet User Manual

Page 2

background image

ENGINE SPECIFICATIONS

General

Cooling System

Make

Generac

Cooling System Type

Pressurized, Closed Recovery

EPA Emissions Compliance

Stationary Emergency

Water Pump Flow

54 gal/min

EPA Emissions Reference

See Emissions Data Sheet

Fan Type

Puller

Cylinder #

6

Fan Speed (rpm)

1632

Type

Inline

Fan Diameter mm (in.)

990 (39)

Displacement - L

13.3

Coolant Heater Wattage

2000

Bore - mm (in.)

136.91 (5.39)

Coolant Heater Standard Voltage

240VAC

Stroke - mm (in.)

150.11 (5.91)

Compression Ratio

10.5:1

Fuel System

Intake Air Method

Turbocharged/Aftercooled

Fuel Type

Natural Gas

Number of Main Bearings

7

Carburetor

Down Draft

Connecting Rods

Carbon Steel

Secondary Fuel Regulator

Standard

Cylinder Head

Cast Iron, Overhead Valve

Fuel Shut Off Solenoid

Standard

Cylinder Liners

Wet, Replaceable

Operating Fuel Pressure

11" - 15" H

2

O

Ignition

Altronic CD1

Pistons

Heat Resistant Alloy

Engine Electrical System

Crankshaft

Die-Forged Carbon Steel

System Voltage

24VDC

Lifter Type

Solid

Battery Charging Alternator

Std

Intake Valve Material

Special Heat-Resistant Steel

Battery Size (at 0ºC)

1155 CCA

Exhaust Valve Material

Iconel Alloy, High Temp

Battery Group

8D

Hardened Valve Seats

High Temp Alloy Stellite Faced

Battery Voltage

12VDC

Ground Polarity

Negative

Lubrication System
Oil Pump Type

Gear

Oil Filter Type

Full-Flow, Cartridge

Crankcase Capacity - L (qts)

27 (28.5)

ALTERNATOR SPECIFICATIONS

Standard Model

520mm

Voltage Regulator Type

Full Digital

Poles

4

Number of Sensed Phases

3

Field Type

Revolving

Regulation Accuracy (Steady State)

± 0.25%

Insulation Class - Rotor

H

Insulation Class - Stator

H

Engine Governing

Total Harmonic Distortion

< 5%

Governor

Electronic

Telephone Interference Factor (TIF)

< 50

Frequency Regulation (Steady State)

± 0.25%

Standard Excitation

Permanent Magnent

Bearings

Sealed Ball

Coupling

Gear Drive

Load Capacity - Standby

100%

Prototype Short Circuit Test

Yes

CODES AND STANDARDS COMPLIANCE (WHERE APPLICABLE)

NFPA 99

BS5514

NFPA 110

SAE J1349

ISO 8528-5

DIN6271

ISO 1708A.5

IEEE C62.41 TESTING

ISO 3046

NEMA ICS 1

2 of 5

Rating Definitions:
Standby – Applicable for a varying emergency load for the duration of a utility power outage with no overload capability. (Max. load factor = 70%)
Prime – Applicable for supplying power to a varying load in lieu of utility for an unlimited amount of running time. (Max. load factor = 80%) A 10% overload capacity is available for 1 out of every
12 hours.

G275LG

application and engineering data

G275LG 275kW

24VDC

Std

1155 CCA

8D

(2) 12VDC

Negative