beautypg.com

Technical data – Milton CAT D60-6 60 kW Spec Sheet User Manual

Page 4

background image

STANDBY 60 ekW 75 kVA

PRIME 55 ekW 67 kVA

60 Hz 1800 rpm 480 Volts

TECHNICAL DATA

Open Generator Set – 1800 rpm/60 Hz/480 Volts

P3468A

P3468B

Tier 3

STANDBY

PRIME

Generator Set Package Performance
Genset power rating @ 0.8 pf
Genset power rating with fan

75.0 kVA

60.0 ekW

68.8 kVA

55.0 ekW

Fuel Consumption
100% load with fan
75% load with fan
50% load with fan

19.6 L/hr
17.0 L/hr
13.1 L/hr

5.2 gal/hr
4.5 gal/hr
3.5 gal/hr

18.9 L/hr
16.1 L/hr
12.4 L/hr

5.0 gal/hr
4.3 gal/hr
3.3 gal/hr

Cooling System

1

Air flow restriction (system)
Engine coolant capacity with radiator/exp. tank
Engine coolant capacity
Radiator coolant capacity

0.12 kPa
16.5 L
9.5 L
7.0 L

0.48 in. water
4.4 gal
2.5 gal
1.8 gal

0.12 kPa
16.5 L
9.5 L
7.0 L

0.48 in. water
4.4 gal
2.5 gal
1.8 gal

Inlet Air
Combustion air inlet flow rate

5.9 m³/min

208.4 cfm

5.9 m³/min

208.4 cfm

Exhaust System
Exhaust stack gas temperature
Exhaust gas flow rate
Exhaust flange size (internal diameter)
Exhaust system back pressure (maximum)

547.0°C
14.7 m³/min
63.5 mm
15 kPa

1017 °F
519 cfm
2.5 in
60.2 in. water

525.0°C
14.4 m³/min
63.5 mm
15 kPa

977 °F
509 cfm
2.5 in
60.2 in. water

Heat Rejection
Heat rejection to coolant (total)
Heat rejection to exhaust (total)
Heat rejection to atmosphere from engine
Heat rejection to atmosphere from generator

49.6 kW
66.9 kW
14.9 kW
6.1 kW

2821 Btu/min
3805 Btu/min
847.3 Btu/min
346.9 Btu/min

46.7 kW
65.9 kW
10.8 kW
5.4 kW

2656 Btu/min
3742 Btu/min
614.2 Btu/min
307.1 Btu/min

Alternator

2

Motor starting capability @ 30% voltage dip
Frame
Temperature rise

163 skV
LC2014HF
105°C

189°F

163 skV
LC2014HF
105°C

189°F

Lubrication System
Total oil capacity
Oil pan

8.4 L
6.9 L

2.2 gal
1.8 gal

8.4 L
6.9 L

2.2 gal
1.8 gal

1

For ambient and altitude capabilities consult your Cat dealer. Airflow restriction (system) is added to existing restriction from factory.

2

Generator temperature rise is based on a 40°C (104°F) ambient per NEMA MG1-32.